[ Log In ]
[ Register ]

Question #: 13778

Question: what are the vfd spindle error codes

Current Solution

Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

If you have an HY series VFD, the fault codes are below:

OC-1: Over-current during ramp up or over-current at constant speed.
Recommended actions: 1, 2, 3, 4

OC-1: Over-current during ramp up or over-current at constant speed.
Recommended actions: 1, 2, 5, 6

OC-2: Over-current at deceleration or over-current at stop.
Recommended actions: 1, 7, 2, 9, 10

dL: Output short circuit.
Recommended actions: 11, 1, 10

Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
Recommended actions: 12, 13

Fb: Fuse break.
Recommended actions: 14, 10

Lu: Low voltage.
Recommended actions: 15, 16, 17

OH: Over heat of inverter.
Recommended actions: 18, 19, 20

OL-1: Inverter overload 150% per minute
Recommended actions: 2, 21, 22

OL-2: Motor overload 150% per minute.
Recommended actions: 21, 23, 24, 25, 26, 21

dT: Motor over-torque
Recommended actions: 21, 23

E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
Recommended action: 27

bt: Braking transistor damage.
Recommended action: 27

CPu: CPU fault.
Recommended action: 27

E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
Recommended action: 27


List of recommended actions:
If error shows at ramp up or at constant speed:
1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
3. Extend the ramp-up time
4. Decrease the torque and increase the set value.
5. Check if the motor is blocked and if there is a sudden change in load.
6. Check if there is a sudden chance in the power supply voltage.
7. Extend ramp down time
9. DC breaking is too high. Decrease DC breaking
10. Replace the inverter.
11. Check to see if there is a short circuit with the connection wire of the motor.
12. Extend the ramp-down time or add a breaking resistor.
13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
14. Send the inverter for repair.
15. Check whether the input voltage is normal
16. check whether there is a sudden change in load.
17. Check whether there is any phase missing.
18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
19. Check the ambient temperature in the space that the inverter is placed.
20. Check for adequate ventilation for the inverter where it is placed.
21. Check for jamming or any sudden change with respect to mechanical load.
22. Set the V/F curve correctly.
23. The motor is too small.
24. The motor is hot and the insulation of the motor degraded.
25. Check if the voltage has a large variance.
26. Check if there is a phase missing.
27. Contact the supplier

Additional Information:
I have cnc wood carving machine 1325 the inverter showing error 0006

Additional Information:
What is uc3 error

Additional Information:
My inverter read error oc-1 high frequency how you can help me please


Additional Information:
My inverter read error oc-1 high frequency how you can help me please


Additional Information:
203

Additional Information:
E2 error

Additional Information:
Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

Additional Information:


Additional Information:
what does it mean when my spindle VFD shows E o and stops.


Additional Information:
Vfd er.01.5c

Additional Information:
CPFO error displayed reason

Additional Information:
Solve it

Additional Information:
My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
Frequency to Frequency track start. whats wrong with the vactory setting?

Additional Information:
Er20

Additional Information:
Fault 503

Additional Information:
Fault 503

Additional Information:
What VFD do you have?

Respond:

Other Possible Solutions to this Question

  • vfd and spindle error codes listing

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Click the link to respond:
    vfd and spindle error codes listing

  • spindle vfd error codes

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Click the link to respond:
    spindle vfd error codes

  • WHAT ARE THE OUTPUT INVERTER (VFD) CONNECTIONS TO SPINDLE?

    U - Pin1
    V - Pin2
    W - Pin3
    Pin4 Dead

    Additional Information:
    My home made cnc is a big problem with my NC connection. When in start my spindle it will be gone wrong. It will be limith switch problem anytime. Need help thanks.

    Click the link to respond:
    WHAT ARE THE OUTPUT INVERTER (VFD) CONNECTIONS TO SPINDLE?

  • WHAT ARE THE SPINDLE INVERTERS (VFD) INPUT AC CONNECTIONS FROM WALL OUTLET?

    Input to VFD:
    240V Active - R
    240V Neutral - S
    Ground - E

    Click the link to respond:
    WHAT ARE THE SPINDLE INVERTERS (VFD) INPUT AC CONNECTIONS FROM WALL OUTLET?

  • I WIRED MY VFD (2.2KW VERSION) AND TRIED TEST RUNNING THE SPINDLE. CONFIGURED TO YOUR SPECS ON THIS WEBSITE, ONLY ISSUE IS WE GOT AN ERROR CODE. ERR 02, DO YOU KNOW WHAT IS? OR HAVE A LIST OF CODES? THANK

    Can you provide the model number of your VFD?

    Yes, I have the "YL600 - 2S - 2K20"

    It just came with a small booklet that is all in Chinese...

    Click the link to respond:
    I WIRED MY VFD (2.2KW VERSION) AND TRIED TEST RUNNING THE SPINDLE. CONFIGURED TO YOUR SPECS ON THIS WEBSITE, ONLY ISSUE IS WE GOT AN ERROR CODE. ERR 02, DO YOU KNOW WHAT IS? OR HAVE A LIST OF CODES? THANK

  • I wired my vfd (2.2kw version) and tried test running the spindle. I configured to your specs on this website, only issue is we got an error code. Err 02, do you know what this is? OR have a list of error codes? Thank you

    Can you provide the model number of your VFD?

    Yes, I have the "YL600 - 2S - 2K20"

    It just came with a small booklet that is all in Chinese...

    Click the link to respond:
    I wired my vfd (2.2kw version) and tried test running the spindle. I configured to your specs on this website, only issue is we got an error code. Err 02, do you know what this is? OR have a list of error codes? Thank you

  • spindle error codes

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Click the link to respond:
    spindle error codes

  • What are the noise levels of the 1.5 Kw and 2.2Kw spindles?

    The noise level of the 1.5 kW and the 2.2 kW are very similar. The noise level is considerably quieter than typical routers. I am going to add sound db levels to this FAQ a bit later.

    Additional Information:
    The db (decibels) reading for the spindle is 70 and an 890 Porter Cable router (a lower powered tool than the spindle) measured 90 db. Both measurements were taken in the same environment and measured at the same distance from the tool.

    Additional Information:
    Practically silent. The inverter makes more noise!

    Additional Information:
    Practically silent. The inverter makes more noise!

    Click the link to respond:
    What are the noise levels of the 1.5 Kw and 2.2Kw spindles?

  • What brand is the 2.2 kW spindle? Same for the VFD. Thanks.

    Spindles are generally covered up to 1 year after date of purchase. We do not repair them in house, but we do work with our manufacturer to replace defective units. Generally if you have a defective unit covered under warranty, we will issue a replacement.

    Click the link to respond:
    What brand is the 2.2 kW spindle? Same for the VFD. Thanks.

  • What size of wire do you use to connect the VFD to the spindle?

    The type of wire that should be used between the spindle and the VFD (Variable Frequency Driver also called the inverter) should be of stranded type and we use between 18 and 16 AWG.

    The total current is divided among the three coil wires, therefor a wire gauge of 16 should be sufficient.

    Currently we use 20AWG 4 conductor.

    Additional Information:

    Click the link to respond:
    What size of wire do you use to connect the VFD to the spindle?

  • Is the 4kv spindle constructed using two or four bearings and what size collets are included with the spindle/vfd combo?

    Yes, all of the spindles come with collets. The collets have a 1/4" (6.35mm) bore for end mills that have a 1/4" shank. The ER specification is different for the 1.5kW (ER-11) and the 2.2kW (ER-20).

    Click the link to respond:
    Is the 4kv spindle constructed using two or four bearings and what size collets are included with the spindle/vfd combo?

  • What are the dimension of the greenBull 4x with dual laser/spindle head?

    The shipping weight (with crate) of the greenBull 4X CNC machine with the dual laser/spindle head is 230 lbs. The overall dimensions are: 76"x36"x27". The crate is typicall send via freight.

    Click the link to respond:
    What are the dimension of the greenBull 4x with dual laser/spindle head?

  • what does the error code on my vfd mean?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Click the link to respond:
    what does the error code on my vfd mean?

  • What is the HP of the 2.2KW spindle

    The 2.2kW spindle outputs approximately 3 HP (Horse Power).

    Click the link to respond:
    What is the HP of the 2.2KW spindle

  • Are there any other manuals for the VFD that comes with the 2.2kw spindle?

    We have manuals for the VFD rather than the spindles. Can you specify what issue you may be having so we can help you better?

    Additional Information:
    I am having trouble wiring the VFD. (From the wall outlet to the VFD) I think the manual or setup guide on your website is wrong. The two diagrams show two different sets of terminals on the page.

    Also, do you have a video or other documentation on programming the VFD? Your videos and documentation looks like it only covers the 1.2kw version. Are the two different spindles from different manufacturers?

    Click the link to respond:
    Are there any other manuals for the VFD that comes with the 2.2kw spindle?

  • What length of wire do you recommend for the black toe (2'x4') between the spindle and VFD?

    The length of the cable from the VFD (Variable Frequency Drive) to the actual spindle should be about the same as the z-axis cable from the z-axis motor to the z-axis driver which is recommended at 11 feet. This is locating the VFD about at the midpoint of the machine.

    Click the link to respond:
    What length of wire do you recommend for the black toe (2'x4') between the spindle and VFD?

  • What is the warranty on your 2.2KW spindle

    We honor a one year warranty on most parts like main machine components, structural parts, mechanical parts and some electronic parts including spindles.

    Click the link to respond:
    What is the warranty on your 2.2KW spindle

  • What size water tubing fits on the spindle?

    The spindle water inlet and outlet fittings are 1/4 Inside Diameter and 3/8 Outside Diameter.

    You can find the silicone tubes here:
    https://buildyourcnc.com/item/pneumatic-hydraulic-silicone-tubing

    This fitting will connect to the pump (1/2" male to 1/4" female):
    https://buildyourcnc.com/item/pneumatic-hydraulic-Tube-Fitting-Female-to-Male

    And this fitting will provide a reduced barbed size (1/4") for the tube:
    https://buildyourcnc.com/item/pneumatic-hydraulic-Tube-Fitting-Barbed-to-Male

    Click the link to respond:
    What size water tubing fits on the spindle?

  • What size collet can the 2.2kW spindle use?

    All of our spindles come standard with a 1/4" collet. The 2.2kw, and 4.0kw, can be upgraded to a 1/2" collet with a separate purchase.

    Click the link to respond:
    What size collet can the 2.2kW spindle use?

Get Help with:
This Product
Orders
Tech Support
Sales
This Product
Order Query
Tech Support
Sales
Not logged in. Log In Register
Track Order(s)
View Order(s)
I Want to Schecule a One-On-One Paid Tech Support Session
Book an Appointment Pertaining to a BuildYourCNC Product (Free)
Ask a Quesion Below (Free):
Book an Appointment Pertaining Other Equipment ($60/half hour)
Book an Immedite Appointment Pertaining Other Equipment ($120/half hour)
Ask a Quesion Below (Free):
Waiting for response... I may not answer immediately, but I was notified on my cellular phone so my response is forthcoming. If I don't respond immediately, you can always go to the [My Account] page to see all of our chats at any time.