Question #: 13889

Question: what does the error code on my vfd mean?

Current Solution

Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

If you have an HY series VFD, the fault codes are below:

OC-1: Over-current during ramp up or over-current at constant speed.
Recommended actions: 1, 2, 3, 4

OC-1: Over-current during ramp up or over-current at constant speed.
Recommended actions: 1, 2, 5, 6

OC-2: Over-current at deceleration or over-current at stop.
Recommended actions: 1, 7, 2, 9, 10

dL: Output short circuit.
Recommended actions: 11, 1, 10

Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
Recommended actions: 12, 13

Fb: Fuse break.
Recommended actions: 14, 10

Lu: Low voltage.
Recommended actions: 15, 16, 17

OH: Over heat of inverter.
Recommended actions: 18, 19, 20

OL-1: Inverter overload 150% per minute
Recommended actions: 2, 21, 22

OL-2: Motor overload 150% per minute.
Recommended actions: 21, 23, 24, 25, 26, 21

dT: Motor over-torque
Recommended actions: 21, 23

E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
Recommended action: 27

bt: Braking transistor damage.
Recommended action: 27

CPu: CPU fault.
Recommended action: 27

E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
Recommended action: 27


List of recommended actions:
If error shows at ramp up or at constant speed:
1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
3. Extend the ramp-up time
4. Decrease the torque and increase the set value.
5. Check if the motor is blocked and if there is a sudden change in load.
6. Check if there is a sudden chance in the power supply voltage.
7. Extend ramp down time
9. DC breaking is too high. Decrease DC breaking
10. Replace the inverter.
11. Check to see if there is a short circuit with the connection wire of the motor.
12. Extend the ramp-down time or add a breaking resistor.
13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
14. Send the inverter for repair.
15. Check whether the input voltage is normal
16. check whether there is a sudden change in load.
17. Check whether there is any phase missing.
18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
19. Check the ambient temperature in the space that the inverter is placed.
20. Check for adequate ventilation for the inverter where it is placed.
21. Check for jamming or any sudden change with respect to mechanical load.
22. Set the V/F curve correctly.
23. The motor is too small.
24. The motor is hot and the insulation of the motor degraded.
25. Check if the voltage has a large variance.
26. Check if there is a phase missing.
27. Contact the supplier

Additional Information:
I have cnc wood carving machine 1325 the inverter showing error 0006

Additional Information:
What is uc3 error

Additional Information:
My inverter read error oc-1 high frequency how you can help me please


Additional Information:
My inverter read error oc-1 high frequency how you can help me please


Additional Information:
203

Additional Information:
E2 error

Additional Information:
Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

Additional Information:


Additional Information:
what does it mean when my spindle VFD shows E o and stops.

Respond:

Other Possible Solutions to this Question

  • what are the vfd spindle error codes

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.

    Click the link to respond:
    what are the vfd spindle error codes

  • Why does my VFD show the error er.04?

    The Er.04 (if you are using the YL VFD), generally refers to the ramping up and ramping down of the spindle, but it can be a result of a short circuit between the VFD and the spindle. You can increase the time the spindle accelerates (ramps up to the set rpm/frequency).

    Click the link to respond:
    Why does my VFD show the error er.04?

  • what does it mean when my spindle VFD inverter shows OC-2?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.

    Click the link to respond:
    what does it mean when my spindle VFD inverter shows OC-2?

  • My VFD has started to dL error at startup, what could be the issue?

    The DL error usually means that there is a short in the wiring going from the VFD to the Spindle. First remove the spindle connection and run the VFD. If "DL" does not appear then this means the short is on the spindle itself. Remember to double check your wiring and to use heat shrink on the soldering points to prevent any shorts or arcing between the points.

    Additional Information:


    Additional Information:
    My drive showing dp when it start


    Additional Information:


    Additional Information:


    Additional Information:


    Additional Information:
    My dovol VFD is telling me do what should I do

    Click the link to respond:
    My VFD has started to dL error at startup, what could be the issue?

  • When using the laser controller, what does "engrave beyond border limit" mean?

    LaserCAD: Engrave beyond border limit.

    This is caused by a sweeping motion that is too fast and where the acceleration is too slow. My recommended action would be to keep the acceleration the way it is and slow down the speed of the engrave sweeping motion. I typically use around 200-300 mm/sec and make sure that the axis sweep motion is the nozzle along the gantry, not the gantry itself. The gantry will have too much inertia to sweep, but the nozzle is very light and can sweep very quickly.

    Specifically, what is happening with the engrave beyond border limit is where that axis is not able to slow down fast enough to not hit the border. For instance, imagine a car going 100 mph and it needs to stop within 30 feet. This would not be possible because the deceleration is not high enough.

    Click the link to respond:
    When using the laser controller, what does "engrave beyond border limit" mean?

  • my vfd is showing an error code

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.

    Click the link to respond:
    my vfd is showing an error code

  • I WIRED MY VFD (2.2KW VERSION) AND TRIED TEST RUNNING THE SPINDLE. CONFIGURED TO YOUR SPECS ON THIS WEBSITE, ONLY ISSUE IS WE GOT AN ERROR CODE. ERR 02, DO YOU KNOW WHAT IS? OR HAVE A LIST OF CODES? THANK

    Can you provide the model number of your VFD?

    Yes, I have the "YL600 - 2S - 2K20"

    It just came with a small booklet that is all in Chinese...

    Click the link to respond:
    I WIRED MY VFD (2.2KW VERSION) AND TRIED TEST RUNNING THE SPINDLE. CONFIGURED TO YOUR SPECS ON THIS WEBSITE, ONLY ISSUE IS WE GOT AN ERROR CODE. ERR 02, DO YOU KNOW WHAT IS? OR HAVE A LIST OF CODES? THANK

  • what horizon does the sun set?

    The sun sets on the western horizon.

    Click the link to respond:
    what horizon does the sun set?

  • I wired my vfd (2.2kw version) and tried test running the spindle. I configured to your specs on this website, only issue is we got an error code. Err 02, do you know what this is? OR have a list of error codes? Thank you

    Can you provide the model number of your VFD?

    Yes, I have the "YL600 - 2S - 2K20"

    It just came with a small booklet that is all in Chinese...

    Click the link to respond:
    I wired my vfd (2.2kw version) and tried test running the spindle. I configured to your specs on this website, only issue is we got an error code. Err 02, do you know what this is? OR have a list of error codes? Thank you

  • what do you mean by integrated computer on the black tooth?

    The blackTooth comes in 2 combinations, 1st being with only the structure and electronic components, hardware. Without any computer parts(provided by customer)
    2nd will be structure and electronic components/hardware and computer parts(motherboard, PSU, etc.) So only input device must be provided(keyboard,mouse,screen).

    Additional Information:

    Click the link to respond:
    what do you mean by integrated computer on the black tooth?

  • vfd error 4 code, how do I fix this?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.

    Click the link to respond:
    vfd error 4 code, how do I fix this?

  • Can we get a VFD Error Code listing?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.

    Click the link to respond:
    Can we get a VFD Error Code listing?

  • vfd and spindle error codes listing

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.

    Click the link to respond:
    vfd and spindle error codes listing

  • What are the physical dimensions of the 2.2kw VFD?

    On Monday, when I get back into the office, I will provide the dimensions for the 2.2kW spindle and I will also provide a drawing of these dimensions on the spindle 2.2kW page. Thanks.

    Additional Information:
    Spindle dimensional specifications:

    - Overall diameter is 80mm
    - The length of the outer housing is 200 mm
    - Diameter of the extension just below the spindle is 36mm and the length is 12mm
    - The Collet shaft diameter is 11.318 and the collet nut diameter is 16.75mm and both extend from the extension approximately 52.5 mm
    - The overall length is 264.5mm not including the air ports and the electrical connector (outer housing 200mm + extension 12mm + collet shaft and nut 52.5 mm).
    - The air ports extend 20 mm from the top of the spindle

    Click the link to respond:
    What are the physical dimensions of the 2.2kw VFD?

  • Laser; does your new laser controller uses the stander g-code files??

    No, the laser controller does not run standard g-code. Instead it uses a version of a printer control language which provides optimal results when processing detailed images and designs. If you need or want to control your laser with g-code, however, you can do so by running it from a computer using a standard machine control software. You can even set your laser up to operate both ways. Feel free to contact us directly if you need help sorting through your options.

    Click the link to respond:
    Laser; does your new laser controller uses the stander g-code files??

  • vfd error code 4 can we get a VFD error code listing?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.

    Click the link to respond:
    vfd error code 4 can we get a VFD error code listing?

  • What doesn't come with the electronics that I will need so it will work?

    Here is a list of the parts needed to get the electronics combo functioning (parallel or USB interface options):

    - 22 or 24 gauge stranded hookup wire to connect all of the drivers to the USB or parallel interface (terminal to terminal connections),
    - 18 gauge stranded hookup wire to connect the drivers to the power supply,
    - a power cable (extension cord) to connect from the power outlet to the power supply,
    - 4 conductor cable to connect the drivers to the stepper motors,
    - a USB cable to connect from the computer to the USB interface (or for power to the parallel interface),
    - for the parallel interface, a parallel cable is needed (male to male db-25),
    - a computer (for parallel interface, the computer will need a parallel port and if the computer does not contain a parallel interface, the motherboard may have a header for it, or you can purchase a parallel adapter to plug into the motherboard, very inexpensive),
    - cnc control software: for the USB interface, you will need planet-cnc software, for the parallel interface, you can use any industry standard cnc control software (the typical is Mach3 for Windows, or EMC2 or Linuxcnc for Linux (Linuxcnc.org).

    5v power supply is not needed. The 5 volts signal level power is derived from the computer through USB on both types of interfaces.

    Click the link to respond:
    What doesn't come with the electronics that I will need so it will work?

  • WHAT DOES COPYRIGHT MEAN

    Copyright, a form of intellectual property law, protects original works of authorship including literary, dramatic, musical, and artistic works, such as poetry, novels, movies, songs, computer software, and architecture. Copyright does not protect facts, ideas, systems, or methods of operation, although it may protect the way these things are expressed

    Click the link to respond:
    WHAT DOES COPYRIGHT MEAN

  • What settings does I use for controlling the spindle in StepCon/Linuxcnc?

    LinuxCNC has excellent documents; however, I would like to offer our help in case you don't understand the information on that page. So, please use this FAQ (Question #: 13233) to state your questions by submitting additional information below.

    The LinuxCNC spindle control page is found here: http://linuxcnc.org/docs/html/examples/spindle.html

    Additional Information:
    After reading the LinuxCNC page my first questions would be can the spindle be controlled by PWM signal? Also, what pin on the parallel port would I set to Spindle Enable and FRW?

    Additional Information:
    To connect your computer to the VFD, use a USB to RS-485 interface. RS-485 is just a serial interface protocol that uses standard 0 to +5 voltage TTL signal levels for communication (as opposed to RS-232 which uses -12v and +12 for signal level changes).

    Get a high quality interface to reduce any issues during the process. The VFD should have two terminals labeled RS+ and RS-. The USB to RS-485 adapter should have this labeled on it as well so the connections should be relatively straight forward.

    In the VFD parameters:
    PD001: 2 to accept RS485 commands
    PD002: 2 to accept frequency comands
    PD163: 1 to RS485 slave address:1
    PD164: 1 RS485 baud rate 9600
    PD165: 3 8bit, no parity, 1 stop bit

    Make sure LinuxCNC is also set accordingly:

    The PIN14 and PIN16 in the stepconf wizard should be set to unused because you don't want LinuxCNC to be outputting unnecessary signals.

    In the options step of the stepconf wizard:
    - Check the Include Halui user interface component.
    - Check the Include custom PyVCP GUI panel.
    - Check Spindle speed display

    You will want to edit the custom.hal text file located in the folder that was created from the stepconf wizard. Add these following lines:
    loadusr -Wn vfd hy_vfd -n vfd -d /dev/ttyUSB0 -p none -r 9600
    net spindle-cmd-rpm-abs => vfd.speed-command
    net spindle-cw motion.spindle-forward => vfd.spindle-forward
    net spindle-ccw motion.spindle-reverse => vfd.spindle-reverse
    net on motion.spindle-on => vfd.spindle-on

    The dev folder in linux is typically used for interfacing devices and peripherals to the computer as these devices are communicated by simple memory addresses and these files are linked directly to these addresses.

    Under the custom_postgui.hal file, change this line:

    from: sets spindle-at-speed true
    to: net spindle-at-speed => cfd.spindle_at_speed

    and add the line:

    setp vfd.enable 1

    When you start LinuxCNC, you will a spindle section with the reverse and forward buttons, a stop button and - and + buttons. Use these buttons to conform that the spindle is functioning properly. The spindle speed indicator in LinuxCNC will show the spindle speed and you can confirm that this is equal to the speed indicated on the VFD.


    Credit for this helpful information goes to:


    Additional information was also added by us to provide a better understanding.

    Click the link to respond:
    What settings does I use for controlling the spindle in StepCon/Linuxcnc?