Question: vfd error 4 code, how do I fix this?

Current Solution

Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

If you have an HY series VFD, the fault codes are below:

OC-1: Over-current during ramp up or over-current at constant speed.
Recommended actions: 1, 2, 3, 4

OC-1: Over-current during ramp up or over-current at constant speed.
Recommended actions: 1, 2, 5, 6

OC-2: Over-current at deceleration or over-current at stop.
Recommended actions: 1, 7, 2, 9, 10

dL: Output short circuit.
Recommended actions: 11, 1, 10

Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
Recommended actions: 12, 13

Fb: Fuse break.
Recommended actions: 14, 10

Lu: Low voltage.
Recommended actions: 15, 16, 17

OH: Over heat of inverter.
Recommended actions: 18, 19, 20

OL-1: Inverter overload 150% per minute
Recommended actions: 2, 21, 22

OL-2: Motor overload 150% per minute.
Recommended actions: 21, 23, 24, 25, 26, 21

dT: Motor over-torque
Recommended actions: 21, 23

E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
Recommended action: 27

bt: Braking transistor damage.
Recommended action: 27

CPu: CPU fault.
Recommended action: 27

E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
Recommended action: 27


List of recommended actions:
If error shows at ramp up or at constant speed:
1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
3. Extend the ramp-up time
4. Decrease the torque and increase the set value.
5. Check if the motor is blocked and if there is a sudden change in load.
6. Check if there is a sudden chance in the power supply voltage.
7. Extend ramp down time
9. DC breaking is too high. Decrease DC breaking
10. Replace the inverter.
11. Check to see if there is a short circuit with the connection wire of the motor.
12. Extend the ramp-down time or add a breaking resistor.
13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
14. Send the inverter for repair.
15. Check whether the input voltage is normal
16. check whether there is a sudden change in load.
17. Check whether there is any phase missing.
18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
19. Check the ambient temperature in the space that the inverter is placed.
20. Check for adequate ventilation for the inverter where it is placed.
21. Check for jamming or any sudden change with respect to mechanical load.
22. Set the V/F curve correctly.
23. The motor is too small.
24. The motor is hot and the insulation of the motor degraded.
25. Check if the voltage has a large variance.
26. Check if there is a phase missing.
27. Contact the supplier

Additional Information:
I have cnc wood carving machine 1325 the inverter showing error 0006

Additional Information:
What is uc3 error

Additional Information:
My inverter read error oc-1 high frequency how you can help me please


Additional Information:
My inverter read error oc-1 high frequency how you can help me please


Additional Information:
203

Additional Information:
E2 error

Additional Information:
Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

Additional Information:


Additional Information:
what does it mean when my spindle VFD shows E o and stops.


Additional Information:
Vfd er.01.5c

Additional Information:
CPFO error displayed reason

Additional Information:
Solve it

Additional Information:
My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
Frequency to Frequency track start. whats wrong with the vactory setting?

Additional Information:
Er20

Additional Information:
Fault 503

Additional Information:
Fault 503

Additional Information:
What VFD do you have?

Respond:

Other Possible Solutions to this Question

  • Why does my VFD show the error er.04?

    The Er.04 (if you are using the YL VFD), generally refers to the ramping up and ramping down of the spindle, but it can be a result of a short circuit between the VFD and the spindle. You can increase the time the spindle accelerates (ramps up to the set rpm/frequency).

    Click the link to respond:
    Why does my VFD show the error er.04?

  • my vfd is showing an error code

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Click the link to respond:
    my vfd is showing an error code

  • The mach3 USB card requires 24V, how do I supply this?

    If you are using a spindle with a VFD, there is a 24 volt power supply that will provide the correct power for the V+ and V- on the Mach3 USB. The 12V option is only if you are using the limit switches on that side of the board, but if you are using it to control spindle speed and for the outputs, it's best to use a 24V power supply, or the 24V output on the VFD.

    Additional Information:
    Closed loop

    Click the link to respond:
    The mach3 USB card requires 24V, how do I supply this?

  • my x motor seems to ignore some movements causing it to be innacurate, how do i fix this?

    If one or more motor is not responding, please follow the troubleshooting directions below:

    For parallel Bob only! Make sure both the parallel and USB are connected.

    Re-check wiring, and connections for continuity (no breaks in the wires) and check for correct wiring locations from driver to BoB.
    Check dip switch settings on the driver.
    Check components, by swapping the motors (ex. y-axis motor to z or x-axis driver and z or x-axis motor to y-axis driver) to check if motor functions on another driver.
    Depending on software check step low active (mach 3) or invert pulse (planet-cnc) for the axis which is not responding.
    Mach 3 - config/port & pins/motor outputs / Planet-CNC - file/settings/axes

    Click the link to respond:
    my x motor seems to ignore some movements causing it to be innacurate, how do i fix this?

  • I want to fix the tramming issue, how can I measure this

    You can measure the tramming angle by putting a long L shaped rod that will fit into the spindle's collet and affix a piece that will tough the table to the other end of the rod. Rotate the rod to determine how far out you are. The longer the rod, the more accurate the measurement will be.

    Click the link to respond:
    I want to fix the tramming issue, how can I measure this

  • what does the error code on my vfd mean?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Click the link to respond:
    what does the error code on my vfd mean?

  • Can we get a VFD Error Code listing?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Click the link to respond:
    Can we get a VFD Error Code listing?

  • what are the vfd spindle error codes

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Click the link to respond:
    what are the vfd spindle error codes

  • vfd error code 4 can we get a VFD error code listing?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Click the link to respond:
    vfd error code 4 can we get a VFD error code listing?

  • vfd and spindle error codes listing

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Click the link to respond:
    vfd and spindle error codes listing

  • HOW DO YOU HOOK UP THE VFD TO SPINDLE?

    U - Pin1
    V - Pin2
    W - Pin3
    Pin4 Dead

    Additional Information:
    My home made cnc is a big problem with my NC connection. When in start my spindle it will be gone wrong. It will be limith switch problem anytime. Need help thanks.

    Click the link to respond:
    HOW DO YOU HOOK UP THE VFD TO SPINDLE?

  • HOW DO YOU HOOK UP THE VFD TO SPINDLE?

    blueChick:

    X-axis
    “CW230 (3.0A) Driver”
    Set to 1/16 Microstep, 2.7A
    Dipswitches: 11001100
    Mach3 Motor Tuning: 1422.22 steps/in

    Y-axis
    “CW230 (3.0A) Driver”
    Set to 1/16 Microstep, 2.7A
    Dipswitches: 11001100
    Mach3 Motor Tuning: 1422.22 steps/in

    Z-axis
    “CW230 (3.0A) Driver”
    Set to 1/4 Microstep, 2.7A
    Dipswitches: 10101100
    Mach3 Motor Tuning: 1600 steps/in

    blackToe:

    X-axis
    “CW230 (3.0A) Driver”
    Set to 1/16 Microstep, 2.7A
    Dipswitches: 11001100
    Mach3 Motor Tuning: 1422.22 steps/in

    Y-axis
    “CW230 (3.0A) Driver”
    Set to 1/16 Microstep, 2.7A
    Dipswitches: 11001100
    Mach3 Motor Tuning: 1422.22 steps/in

    Z-axis
    “CW230 (3.0A) Driver”
    Set to 1/4 Microstep, 2.7A
    Dipswitches: 10101100
    Mach3 Motor Tuning: 1600 steps/in

    blackFoot:

    X-axis
    “CW8060 (6.0A) Driver”
    Set to 1/16 Microstep, 2.7A
    Dipswitches: 11001100 (“0”=down, “1”=up)
    Mach3 Motor Tuning: 914.29 steps/in

    Y-axis
    “CW230 (3.0A) Driver”
    Set to 1/16 Microstep, 2.7A
    Dipswitches: 11001100
    Mach3 Motor Tuning: 1422.22 steps/in

    Z-axis
    “CW230 (3.0A) Driver”
    Set to 1/4 Microstep, 2.7A
    Dipswitches: 10101100
    Mach3 Motor Tuning: 1600 steps/in

    greenBull:

    X-axis
    “CW8060 (6.0A) Driver”
    Set to 5.43A, 1/16 Microstep
    Dipswitches: 01100110 (“0”=down, “1”=up)
    Mach3 Motor Tuning: 914.29 steps/in

    Y-axis
    “CW8060 (6.0A) Driver”
    Set to 5.43A, 1/16 Microstep
    Dipswitches: 01100110
    Mach3 Motor Tuning: 914.29 steps/in

    Z-axis
    “CW8060 (6.0A) Driver”
    Set to 5.43A, 1/4 Microstep
    Dipswitches: 01100100
    Mach3 Motor Tuning: 1600 steps/in

    Click the link to respond:
    HOW DO YOU HOOK UP THE VFD TO SPINDLE?

  • i wanna chains the X with the Y assis how can i do this

    Are you asking if you can change the X and Y axes? Please clarify.

    Additional Information:
    Yes i wanna chains the x with the y axes can i make this with the software ?????

    Click the link to respond:
    i wanna chains the X with the Y assis how can i do this

  • HOW DO YOU SETUP THE SPINDLE INVERTER VFD?

    Change PD001 Source of Run Commands to '1'
    Change PD005 Max operating frequency to 400hz
    Change PD004 base frequency to 400hz
    Change PD003 Main frequency to 400hz
    Change PD006 Intermediate frequency to 2.5
    Change PD008 max voltage to 220v
    Change PD009 Intermediate voltage to 15v
    Change PD010 Min voltage to 8
    Change PD011 frequency lower limit to >100hz (120hz to start)
    Change PD142 7 Amps
    Change PD143 2
    Change PD144 3000

    Note: PD001 had to be changed back to 0 to allow for keypad control.
    Note2: I had to reverse U and V to get the spindle to go forward in FWD. (reverse any two wires, u&v or w&v for example)

    Click the link to respond:
    HOW DO YOU SETUP THE SPINDLE INVERTER VFD?

  • Inverter keeps giving me an over current error (1.5kW inverter error OC-r). However this is now making a cut that is 80% lighter than when I first received it. Do you know any way to fix this?

    Make sure to check all of the connections from the VFD to the Spindle and make sure here isn't any short in the wires. That would be the first thing to look for. If that is not resolving the issue, check the programming parameters related to the current and torque setting to make sure that those are within the expected range.

    Click the link to respond:
    Inverter keeps giving me an over current error (1.5kW inverter error OC-r). However this is now making a cut that is 80% lighter than when I first received it. Do you know any way to fix this?

  • How do I conect the VFD of the spindle to the RS485 connections

    It is not necessary to connect the spindle VFD (Variable Frequency Drive also called an Inverter) to the computer or CNC motion electronics. The VFD can be controlled independently using the control panel on the VFD. The control panel has the ability to control all aspects of the spindle including Speed, Torque, limits, etc. However, you can connect the VFD to the computer so the CNC control program can control the spindle during the CNC Machine operation. You will need to connect the VFD to the computer via a serial conection (in this case, it is the RS-485 protocol).

    The following are instructions on how to connect the VFD to Mach3 via this RS-485 serial connection.

    The first thing you will need is the dynamic link library to pair with mach3 called the Huanyang VFD Mach3 PlugIn. You can find this file at the mach3 support forum here: http://www.machsupport.com/forum/index.php/topic,14182.0.html

    You will also need to download the Microsoft .net 3.5 framework and install it: https://www.microsoft.com/en-us/download/details.aspx?id=21

    Follow the pdf that comes with the library file, but here is a synopsis of what you need to do (I also added a lot more information that may be useful during this process as the manual does not cover the main connections that need to be done):

    You will need to program your VFD so that it knows how to communicate with mach3 and the computer (go into the programming mode of the VFD and change these parameters):
    - PD001 - value 2 - Enables with communication aspect of the VFD
    - PD002 - value 2 - Enables frequency control from the communcations port
    - PD163 - value 1 - VFD address
    - PD164 - value 1 - Baud rate of 9600 (speed of the communication)
    - PD165 - value 3 - 8N1 RTU - 8 bits (that's the size of the word that gets communicated), N (No parity or no error checking) and 1 (1 stop bit)

    Copy the dll file to the PlugIns folder of mach3.

    Connect the RX and TX lines to your computer. There are a couple ways you can do this, but the recommended way would be to use an FTDI USB device which converts a USB to a serial com port. The device will have Rx and Tx connectors to connect to the VFD terminals with the same labels. This method is recommended since serial ports are not as common in computers these days.

    Next, you will need to configure mach3 to use the plugin library. Start mach3 and click on Menu -> config ->Config Plugins. Enable the new plugin by clicking on the red cross on the left column next to the plug in. Restart mach3 after doing this.

    No you need to configure mach3 to use the HuanyangVFD plugin. Go to the ports & pins configuration and select the spindle setup tab. Make sure that the Disable Spindle Relays checkbox is unchecked. We don't want mach3 to output a signal for a relay since the spindle will start up and turn off within the VFD and not from an external relay.

    Next, go to the HuanyangVFD settings by clicking on Menu -> plugin control -> HuanyangVFD. Set the parameters to the same settings you put into the VFD programming. The com port will be shown as new hardward when you plug in the USB FTDI device. A little bubble will be displayed at the bottom right where it will notify you that a new device is being installed (be patient while windows assigns a com port). Alternatively, you can use the windows device manager to see which port was set for the new USB FTDI device). You may need to restart mach3 several times until you get the correct information displayed in the PD001 and PD002 fields. When the com port is correct and the other parameters, like baud and VFD address is the same as you entered in the programming, then the PD001 and PD002 will show the number 2, otherwise, a 99 will appear which means that communication was not successful.

    You can now control the on/off and RPM of the spindle using the RS485 communication between mach3 and the VFD.

    Additional Information:
    The question was how to connect the spindle to the redfy. I did not receive a VFD.
    I have the redFly system and a 2.2kW Spindle - 110V how do i connect the spindle?

    Additional Information:
    If you received a spindle without a VFD, please contact us asap. Our spindle will not work without a VFD.

    Additional Information:
    Hi, how is this setup in mach4?

    Click the link to respond:
    How do I conect the VFD of the spindle to the RS485 connections

  • My spindle inverter is showing an E.o.l.A error.

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Click the link to respond:
    My spindle inverter is showing an E.o.l.A error.

  • spindle vfd error codes

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Click the link to respond:
    spindle vfd error codes

  • Hello, I bought your 110v 2.2kw spindle and vfd. When I turn it on it reaches the full 24000 rpm, but will not let me decrease the speed. How Can I fix this?

    Are you using the control panel (front panel with the speed control knob known as he potentiometer)? Or are you attempting to use the computer to control the speed?

    Additional Information:
    I am using the control panel, however there is no knob on mine, just buttons.

    Click the link to respond:
    Hello, I bought your 110v 2.2kw spindle and vfd. When I turn it on it reaches the full 24000 rpm, but will not let me decrease the speed. How Can I fix this?

Get Help with:
This Product
Orders
Tech Support
Sales
This Product
Order Query
Tech Support
Sales
Not logged in. Log In Register
Track Order(s)
View Order(s)
I Want to Schecule a One-On-One Paid Tech Support Session
Book an Appointment Pertaining to a BuildYourCNC Product (Free)
Ask a Quesion Below (Free):
Book an Appointment Pertaining Other Equipment ($60/half hour)
Book an Immedite Appointment Pertaining Other Equipment ($120/half hour)
Ask a Quesion Below (Free):
Waiting for response... I may not answer immediately, but I was notified on my cellular phone so my response is forthcoming. If I don't respond immediately, you can always go to the [My Account] page to see all of our chats at any time.