Question #: 13621

Question: vfd error 4 code, how do I fix this?

Current Solution

Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

If you have an HY series VFD, the fault codes are below:

OC-1: Over-current during ramp up or over-current at constant speed.
Recommended actions: 1, 2, 3, 4

OC-1: Over-current during ramp up or over-current at constant speed.
Recommended actions: 1, 2, 5, 6

OC-2: Over-current at deceleration or over-current at stop.
Recommended actions: 1, 7, 2, 9, 10

dL: Output short circuit.
Recommended actions: 11, 1, 10

Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
Recommended actions: 12, 13

Fb: Fuse break.
Recommended actions: 14, 10

Lu: Low voltage.
Recommended actions: 15, 16, 17

OH: Over heat of inverter.
Recommended actions: 18, 19, 20

OL-1: Inverter overload 150% per minute
Recommended actions: 2, 21, 22

OL-2: Motor overload 150% per minute.
Recommended actions: 21, 23, 24, 25, 26, 21

dT: Motor over-torque
Recommended actions: 21, 23

E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
Recommended action: 27

bt: Braking transistor damage.
Recommended action: 27

CPu: CPU fault.
Recommended action: 27

E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
Recommended action: 27


List of recommended actions:
If error shows at ramp up or at constant speed:
1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
3. Extend the ramp-up time
4. Decrease the torque and increase the set value.
5. Check if the motor is blocked and if there is a sudden change in load.
6. Check if there is a sudden chance in the power supply voltage.
7. Extend ramp down time
9. DC breaking is too high. Decrease DC breaking
10. Replace the inverter.
11. Check to see if there is a short circuit with the connection wire of the motor.
12. Extend the ramp-down time or add a breaking resistor.
13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
14. Send the inverter for repair.
15. Check whether the input voltage is normal
16. check whether there is a sudden change in load.
17. Check whether there is any phase missing.
18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
19. Check the ambient temperature in the space that the inverter is placed.
20. Check for adequate ventilation for the inverter where it is placed.
21. Check for jamming or any sudden change with respect to mechanical load.
22. Set the V/F curve correctly.
23. The motor is too small.
24. The motor is hot and the insulation of the motor degraded.
25. Check if the voltage has a large variance.
26. Check if there is a phase missing.
27. Contact the supplier

Additional Information:
I have cnc wood carving machine 1325 the inverter showing error 0006

Additional Information:
What is uc3 error

Additional Information:
My inverter read error oc-1 high frequency how you can help me please


Additional Information:
My inverter read error oc-1 high frequency how you can help me please


Additional Information:
203

Additional Information:
E2 error

Additional Information:
Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

Additional Information:


Additional Information:
what does it mean when my spindle VFD shows E o and stops.


Additional Information:
Vfd er.01.5c

Additional Information:
CPFO error displayed reason

Additional Information:
Solve it

Additional Information:
My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
Frequency to Frequency track start. whats wrong with the vactory setting?

Additional Information:
Er20

Additional Information:
Fault 503

Additional Information:
Fault 503

Additional Information:
What VFD do you have?

Additional Information:
When I on the motor the derave right oc2 it move then it stop again

Additional Information:
When I on the motor the derave right oc2 it move then it stop again


Additional Information:
what does it mean when my spindle VFD shows E.Lu.S and stops.

Additional Information:
Dear si my emetron ac drive ERR 05 PROBLEM

Additional Information:
Err04



Additional Information:
Err04


Additional Information:
Error 4

Additional Information:
Error 4

Respond:

Other Possible Solutions to this Question

  • I want to fix the tramming issue, how can I measure this

    You can measure the tramming angle by putting a long L shaped rod that will fit into the spindle's collet and affix a piece that will tough the table to the other end of the rod. Rotate the rod to determine how far out you are. The longer the rod, the more accurate the measurement will be.

    Click the link to add information to this solution:
    I want to fix the tramming issue, how can I measure this

  • The mach3 USB card requires 24V, how do I supply this?

    If you are using a spindle with a VFD, there is a 24 volt power supply that will provide the correct power for the V+ and V- on the Mach3 USB. The 12V option is only if you are using the limit switches on that side of the board, but if you are using it to control spindle speed and for the outputs, it's best to use a 24V power supply, or the 24V output on the VFD.

    Additional Information:
    Closed loop

    Additional Information:
    Can i use 12v in the 24v input

    Click the link to add information to this solution:
    The mach3 USB card requires 24V, how do I supply this?

  • Can we get a VFD Error Code listing?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Additional Information:
    When I on the motor the derave right oc2 it move then it stop again

    Additional Information:
    When I on the motor the derave right oc2 it move then it stop again


    Additional Information:
    what does it mean when my spindle VFD shows E.Lu.S and stops.

    Additional Information:
    Dear si my emetron ac drive ERR 05 PROBLEM

    Additional Information:
    Err04



    Additional Information:
    Err04


    Additional Information:
    Error 4

    Additional Information:
    Error 4

    Click the link to add information to this solution:
    Can we get a VFD Error Code listing?

  • vfd error code 4 can we get a VFD error code listing?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Additional Information:
    When I on the motor the derave right oc2 it move then it stop again

    Additional Information:
    When I on the motor the derave right oc2 it move then it stop again


    Additional Information:
    what does it mean when my spindle VFD shows E.Lu.S and stops.

    Additional Information:
    Dear si my emetron ac drive ERR 05 PROBLEM

    Additional Information:
    Err04



    Additional Information:
    Err04


    Additional Information:
    Error 4

    Additional Information:
    Error 4

    Click the link to add information to this solution:
    vfd error code 4 can we get a VFD error code listing?

  • Why does my VFD show the error er.04?

    The Er.04 (if you are using the YL VFD), generally refers to the ramping up and ramping down of the spindle, but it can be a result of a short circuit between the VFD and the spindle. You can increase the time the spindle accelerates (ramps up to the set rpm/frequency).

    Additional Information:

    Click the link to add information to this solution:
    Why does my VFD show the error er.04?

  • HOW DO YOU HOOK UP THE VFD TO SPINDLE?

    U - Pin1
    V - Pin2
    W - Pin3
    Pin4 Dead

    Additional Information:
    My home made cnc is a big problem with my NC connection. When in start my spindle it will be gone wrong. It will be limith switch problem anytime. Need help thanks.

    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:

    Click the link to add information to this solution:
    HOW DO YOU HOOK UP THE VFD TO SPINDLE?

  • How do I program the 2.2kw VFD to jog with a Digital Input

    It is possible to connect and configure the spindle VFD to the mach3 via an RS485 communication and protocol.

    The first thing you will need is the dynamic link library to pair with mach3 called the Huanyang VFD Mach3 PlugIn. You can find this file at the mach3 support forum here: http://www.machsupport.com/forum/index.php/topic,14182.0.html

    You will also need to download the Microsoft .net 3.5 framework and install it: https://www.microsoft.com/en-us/download/details.aspx?id=21

    Follow the pdf that comes with the library file, but here is a synopsis of what you need to do (I also added a lot more information that may be useful during this process as the manual does not cover the main connections that need to be done):

    You will need to program your VFD so that it knows how to communicate with mach3 and the computer (go into the programming mode of the VFD and change these parameters):
    - PD001 - value 2 - Enables with communication aspect of the VFD
    - PD002 - value 2 - Enables frequency control from the communcations port
    - PD163 - value 1 - VFD address
    - PD164 - value 1 - Baud rate of 9600 (speed of the communication)
    - PD165 - value 3 - 8N1 RTU - 8 bits (that's the size of the word that gets communicated), N (No parity or no error checking) and 1 (1 stop bit)

    Copy the dll file to the PlugIns folder of mach3.

    Connect the RX and TX lines to your computer. There are a couple ways you can do this, but the recommended way would be to use an FTDI USB device which converts a USB to a serial com port. The device will have Rx and Tx connectors to connect to the VFD terminals with the same labels. This method is recommended since serial ports are not as common in computers these days.

    Next, you will need to configure mach3 to use the plugin library. Start mach3 and click on Menu -> config ->Config Plugins. Enable the new plugin by clicking on the red cross on the left column next to the plug in. Restart mach3 after doing this.

    No you need to configure mach3 to use the HuanyangVFD plugin. Go to the ports & pins configuration and select the spindle setup tab. Make sure that the Disable Spindle Relays checkbox is unchecked. We don't want mach3 to output a signal for a relay since the spindle will start up and turn off within the VFD and not from an external relay.

    Next, go to the HuanyangVFD settings by clicking on Menu -> plugin control -> HuanyangVFD. Set the parameters to the same settings you put into the VFD programming. The com port will be shown as new hardward when you plug in the USB FTDI device. A little bubble will be displayed at the bottom right where it will notify you that a new device is being installed (be patient while windows assigns a com port). Alternatively, you can use the windows device manager to see which port was set for the new USB FTDI device). You may need to restart mach3 several times until you get the correct information displayed in the PD001 and PD002 fields. When the com port is correct and the other parameters, like baud and VFD address is the same as you entered in the programming, then the PD001 and PD002 will show the number 2, otherwise, a 99 will appear which means that communication was not successful.

    You can now control the on/off and RPM of the spindle using the RS485 communication between mach3 and the VFD.



    Additional Information:
    This looks easy enough, however, the VFD that came with my spindle is made by Huajiang, not a Huanyang. The parameter codes are different and do not line up with the ones offered in this response.

    Click the link to add information to this solution:
    How do I program the 2.2kw VFD to jog with a Digital Input

  • HOW DO YOU SETUP THE SPINDLE INVERTER VFD?

    Change PD001 Source of Run Commands to '1'
    Change PD005 Max operating frequency to 400hz
    Change PD004 base frequency to 400hz
    Change PD003 Main frequency to 400hz
    Change PD006 Intermediate frequency to 2.5
    Change PD008 max voltage to 220v
    Change PD009 Intermediate voltage to 15v
    Change PD010 Min voltage to 8
    Change PD011 frequency lower limit to >100hz (120hz to start)
    Change PD142 7 Amps
    Change PD143 2
    Change PD144 3000

    Note: PD001 had to be changed back to 0 to allow for keypad control.
    Note2: I had to reverse U and V to get the spindle to go forward in FWD. (reverse any two wires, u&v or w&v for example)

    Additional Information:

    Click the link to add information to this solution:
    HOW DO YOU SETUP THE SPINDLE INVERTER VFD?

  • How do I conect the VFD of the spindle to the RS485 connections

    It is not necessary to connect the spindle VFD (Variable Frequency Drive also called an Inverter) to the computer or CNC motion electronics. The VFD can be controlled independently using the control panel on the VFD. The control panel has the ability to control all aspects of the spindle including Speed, Torque, limits, etc. However, you can connect the VFD to the computer so the CNC control program can control the spindle during the CNC Machine operation. You will need to connect the VFD to the computer via a serial conection (in this case, it is the RS-485 protocol).

    The following are instructions on how to connect the VFD to Mach3 via this RS-485 serial connection.

    The first thing you will need is the dynamic link library to pair with mach3 called the Huanyang VFD Mach3 PlugIn. You can find this file at the mach3 support forum here: http://www.machsupport.com/forum/index.php/topic,14182.0.html

    You will also need to download the Microsoft .net 3.5 framework and install it: https://www.microsoft.com/en-us/download/details.aspx?id=21

    Follow the pdf that comes with the library file, but here is a synopsis of what you need to do (I also added a lot more information that may be useful during this process as the manual does not cover the main connections that need to be done):

    You will need to program your VFD so that it knows how to communicate with mach3 and the computer (go into the programming mode of the VFD and change these parameters):
    - PD001 - value 2 - Enables with communication aspect of the VFD
    - PD002 - value 2 - Enables frequency control from the communcations port
    - PD163 - value 1 - VFD address
    - PD164 - value 1 - Baud rate of 9600 (speed of the communication)
    - PD165 - value 3 - 8N1 RTU - 8 bits (that's the size of the word that gets communicated), N (No parity or no error checking) and 1 (1 stop bit)

    Copy the dll file to the PlugIns folder of mach3.

    Connect the RX and TX lines to your computer. There are a couple ways you can do this, but the recommended way would be to use an FTDI USB device which converts a USB to a serial com port. The device will have Rx and Tx connectors to connect to the VFD terminals with the same labels. This method is recommended since serial ports are not as common in computers these days.

    Next, you will need to configure mach3 to use the plugin library. Start mach3 and click on Menu -> config ->Config Plugins. Enable the new plugin by clicking on the red cross on the left column next to the plug in. Restart mach3 after doing this.

    No you need to configure mach3 to use the HuanyangVFD plugin. Go to the ports & pins configuration and select the spindle setup tab. Make sure that the Disable Spindle Relays checkbox is unchecked. We don't want mach3 to output a signal for a relay since the spindle will start up and turn off within the VFD and not from an external relay.

    Next, go to the HuanyangVFD settings by clicking on Menu -> plugin control -> HuanyangVFD. Set the parameters to the same settings you put into the VFD programming. The com port will be shown as new hardward when you plug in the USB FTDI device. A little bubble will be displayed at the bottom right where it will notify you that a new device is being installed (be patient while windows assigns a com port). Alternatively, you can use the windows device manager to see which port was set for the new USB FTDI device). You may need to restart mach3 several times until you get the correct information displayed in the PD001 and PD002 fields. When the com port is correct and the other parameters, like baud and VFD address is the same as you entered in the programming, then the PD001 and PD002 will show the number 2, otherwise, a 99 will appear which means that communication was not successful.

    You can now control the on/off and RPM of the spindle using the RS485 communication between mach3 and the VFD.

    Additional Information:
    The question was how to connect the spindle to the redfy. I did not receive a VFD.
    I have the redFly system and a 2.2kW Spindle - 110V how do i connect the spindle?

    Additional Information:
    If you received a spindle without a VFD, please contact us asap. Our spindle will not work without a VFD.

    Additional Information:
    Hi, how is this setup in mach4?

    Click the link to add information to this solution:
    How do I conect the VFD of the spindle to the RS485 connections

  • [54] There are 8 wires on this motor. How do you connect to the driver?

    If the motor has 8 wires, you will need to wire the stepper motor in bipolar parallel. This motor (425 oz-in) is wired as follows:

    Red and Blue wires to A+ on driver
    Yellow and Black wires to A- on driver
    White and Brown wires to B+ on driver
    Orange and Green wires to B- on driver

    Click the link to add information to this solution:
    [54] There are 8 wires on this motor. How do you connect to the driver?

  • Hello, I bought your 110v 2.2kw spindle and vfd. When I turn it on it reaches the full 24000 rpm, but will not let me decrease the speed. How Can I fix this?

    Are you using the control panel (front panel with the speed control knob known as he potentiometer)? Or are you attempting to use the computer to control the speed?

    Additional Information:
    I am using the control panel, however there is no knob on mine, just buttons.

    Click the link to add information to this solution:
    Hello, I bought your 110v 2.2kw spindle and vfd. When I turn it on it reaches the full 24000 rpm, but will not let me decrease the speed. How Can I fix this?

  • [79] What size circuit breaker should I use for this VFD?

    The 2.2kW spindle has a power rating of 2.2kW or 2200 watts.

    If the VFD AC voltage input is rated for 220 volts, then 2200 watts / 220 volts is 10 amps, so a 15 or 20 amp breaker will work.

    If the VFD AC voltage input is rated for 110 volts, then 2200 watts / 110 volts is 20 amps, so a 25 or 30 amp breaker will work.

    Additional Information:



    Additional Information:

    Click the link to add information to this solution:
    [79] What size circuit breaker should I use for this VFD?

  • [593] I want this to be 12' long. how much does that cost?

    Machine sizes outside of what is selectable on the home page, or the machine product page require a special quote. You can text me at 832-477-0526 for a quote on a unique configuration.

    Click the link to add information to this solution:
    [593] I want this to be 12' long. how much does that cost?

  • [575] I have motor control boards that have 4 pin input ( Step, Dir, EN, +5V) how do I connect this USB board?

    Connect the XD to the Dir, XP to the Step, and the 5V on the Mach3 USB controller to the +5V.

    Click the link to add information to this solution:
    [575] I have motor control boards that have 4 pin input ( Step, Dir, EN, +5V) how do I connect this USB board?

  • [575] I have motor control boards that have 4 pin input ( Step, Dir, EN, +5V) how do I connect this USB board?

    You can connect the 5V from the Mach3 USB controller to the 5V terminal on the driver, the XP to the Step terminal on the driver and the XD to the Dir terminal on the driver.

    Click the link to add information to this solution:
    [575] I have motor control boards that have 4 pin input ( Step, Dir, EN, +5V) how do I connect this USB board?

  • How do you connect a VFD with R S T to 220 power single phase?

    The below information is for your convenience; however, please seek the guidance of a professional electrician that is experienced with VFDs and electrical motors of this type.

    A VFD (Variable Frequency Drive) for CNC Spindles that have input terminals labeled R, S and T will typically use the R and T for the Black (live) and White (neutral) connections and the PE (protective earth) will connect to ground (green).

    Check this image for reference:
    https://www.buildyourcnc.com/images/SpindleWiring-800.JPG

    With the YL600-2S VFD, we have found that the R and S terminals are used where the R is live and S is neutral. Connect the PE to the green ground connection.





    Additional Information:

    Click the link to add information to this solution:
    How do you connect a VFD with R S T to 220 power single phase?

  • How should I wire the 2.2kw spindle and vfd?

    You can find the wiring diagram for the 2.2kW spindle and, follow through instructions here.
    https://www.buildyourcnc.com/item/spindle-inverter-2!2kw-spindle-novfd#prettyPhoto/8/

    Additional Information:


    Additional Information:
    wiring diagram at spindle top


    Additional Information:


    Additional Information:


    Additional Information:


    Additional Information:
    Can you please provide settings for a 110v 2.2 spindle vfd

    Additional Information:
    Can you please provide settings for a 110v 2.2 spindle vfd

    Click the link to add information to this solution:
    How should I wire the 2.2kw spindle and vfd?

  • My spindle does not turn on. How can I fix it?

    Yes, you can send your electronics to us for repair, or retrofit to work with either Mach3, Mach4 or LinuxCNC. You can send us an email at customerService@buildyourcnc.com to set up your appointment.

    Some of the types of CNC electronics we will consider.

    - We will work on electronics from other manufacturers as long as you are ok with the Mach3, Mach4 or LinuxCNC control software for your CNC machine or CNC router.

    - We will repair or retrofit used CNC electronics.

    - Some customers find that electronics are overwhelming to put together so we will finish these electronics wiring and assembly for you.

    The cost for these includes labor cost for the time it takes to finish the CNC electronics repair or retrofit and for any parts that need to be replaced or added.

    Here is an example of CNC electronics that we worked on for a customer:



    This is the type of response that you can expect to receive after the CNC electronics are repaired or retrofitted to work under Mach3, Mach4 or LinuxCNC. You can see the entire work, which also shows the time involved. We also show what we were able to accomplish at the beginning of the video.

    Click the link to add information to this solution:
    My spindle does not turn on. How can I fix it?

  • [807] What size power supply do I need to this?

    I would recommend either a 36VDC or a 48VDC power supply with 10 amps. Here are links to these power supplied on this website:

    https://buildyourcnc.com/item/electronicsAndMotors-power-supply-24v-36v-48v

    Click the link to add information to this solution:
    [807] What size power supply do I need to this?

Get Help with:
This Product
Orders
Tech Support
Sales
This Product
Order Query
Tech Support
Sales
Not logged in. Log In Register
Track Order(s)
View Order(s)
I Want to Schecule a One-On-One Paid Tech Support Session
Book an Appointment Pertaining to a BuildYourCNC Product (Free)
Ask a Quesion Below (Free):
Book an Appointment Pertaining Other Equipment ($60/half hour)
Book an Immedite Appointment Pertaining Other Equipment ($120/half hour)
Ask a Quesion Below (Free):
Waiting for response... I may not answer immediately, but I was notified on my cellular phone so my response is forthcoming. If I don't respond immediately, you can always go to the [My Account] page to see all of our chats at any time.