This will depend on the VFD you have to identify the correct terminal. The terminal on the VFD will be labeled AI1 typically (Analog Input #1). You will also need to make sure to complete the PWM circuit using the GND terminal on the VFD.
Additional Information:
I have wired my 0-10V signal to the AI1 and GND terminals as suggested. I have also set the PD-01 and PD-02 settings to 1. Still nothing. Is there something else that I am missing?
Additional Information:
Thanks for the information. Can you let me know the model of the VFD that you have?
Additional Information:
VFD Model # YL600-2S-2K20
Additional Information:
Thanks. I will check our resources and documentation to see if there is another programming setting that needs to be changed.
Additional Information:
Does your VFD have a VI terminal?
Additional Information:
No, it does not. The terminals for this VFD are as follows (seperated by dashes "-").
10V-AI1-AO2-PLC-DI5-DI3-DI1-COM
AI2-GND-AO1-DI6-DI4-DI2-FM-24V
Additional Information:
Do you have a PD070 parameter?
PD070 is the main Analog Input parameter.
The options for that parameter is:
0: 0-10V
1: 0-5V
2: 0-20mA
3: 4-20mA
4: 0-10V (4-20mA Stacked)
5: XIA
6: (VI+XIA)/2
7: (3VA+XIA)/4
8: (XIA_XIB)/2
9: Max (XIA, XIB)
10: Min (XIA, XIB)
Additional Information:
There is a PD-00 thru PD-09. PD-07 is currently set to 0.
Additional Information:
It appears that the manual I’m using “Titled YL600” is not the same as your unit. I will check our manuals and find the one that has only PD-00 to PD-09.
Additional Information:
For that VFD, the parameters are P0. The 0 may look like a D on the display.
The parameters that need to be changed for the AI1 to work (Brackets [] around the correct selection):
P0-01: First Motor Control Mode
- 0: Sensorless Vector Control
- 1: Flux Vector Control (FVC)
- [2]: V/F Control
P0-02: Options of Command Source
- 0: Operation Panel Command Channel (LED will be off)
- [1]: Terminal Command Channel (LED will be on)
- 2: Communication Command Channel (LED will flicker)
P0-03: Options of Principle Frequency Source X
- 0: Digital Setting (Preset Frequency P0-08, UP/DOWN modifiable, no power-down memory)
- 1: Digital Setting (Preset Frequency P0-08, UP/DOWN modifiable, with power-down memory)
- [2]: AI1
- 3: AI2
- 4: AI3
- 5: Pulse Setting (DI5)
- 6: Multi Speed Instruction
- 7: Simple PLC
- 8: PID (Proportional Integral Derivative Control)
- 9: Communication Given
P0-11: Upper Limit Frequency Source
- 0: P0-12 (Make sure the P0-12 parameter has the correct max frequency if used)
- [1]: AI1
- 2: AI2
- 3: AI3
- 4: Pulse Setting
- 5: Communication Given
P0-27: Command Source Bundle with Frequency Sources
Single Digit: Options of Operation Panel Command Bundle with Frequency Sources
- 0: No Bundling
- 1: Digital Setting Frequency
- [2]: AI1
- 3: AI2
- 4: AI3
- 5: Pulse Setting (DI5)
- 6: Multi Speed Instruction
- 7: Simple PLC
- 8: PID
- 9: Communication Given
Double Digit: Options of Terminal Command Bundle with Frequency Sources
Hundred Place: Options of Communication Command Bundle with Frequency Sources
Kilobit: Options of Automatic Operation Bundle with Frequency Sources
P2-09: Upper Limit Source of Lower Torque Under Speed Control Mode
- 0: Function Code P2-10 Setting
- [1]: AI1
- 2: AI2
- 3: AI3
- 4: Pulse Setting
- 5: Communication Given
- 6: MIN (Al1, Al2)
- 7: MAX (Al1, Al2)
- Maximum range for options 1-7, accords with P2-10
If you elect to use a different AI#, then configure the parameters (P0-03, P0-11, P0-27 and P2-09) accordingly.
Click the link to add information to this solution:
I'VE BUFFERED A PWM SIGNAL TO 0-10V ANALOG AND I WOULD LIKE USE THAT RUN YOUR 110V 2.2KW SPINDLE VFD. COULD YOU PLEASE DETAIL THE CORRECT WIRING VFD SETTINGS GET WORKING?