Question #: 15446

Question: I HAVE A 2.2KW WATER COOLED SPINDLE WITH YL620-H VFD. THE VFD USES P#-## PROGRAM FORMAT. BELIEVE ALL CORRECT SETTINGS SETUP BUT WHEN TURN UNIT ON, IT SPINS AT ABOUT 200-300 RPM REGARDLESS OF WHAT FREQUENCY CHOOSE. DO YOU PARAMETERS IN THIS FORMAT FOR UNIT? THANK YOUR HELP. HUIBERT MEES

Current Solution

You will need to look for the parameter that controls the run frequency. The frequency can be controlled bu the panel, external terminals, or the RS485 TX/RX terminals (UART protocol). You will want to change that parameter so it uses the panel. If you are referring to the maximum panel dial frequency is only allowing 200-300 rpm, then look for the parameters to control the frequency.

For 200 RPM:
Hz = 200/60 = 3.33 Hz

For 300 RPM:
Hz = 300/60 = 5 Hz

Conversion to RPM:
If you ever find yourself yearning to reverse-engineer the process, the formula is as follows:

RPM = Hz × 60

Look for values that match somewhere between 3 and 5 in your frequency parameters and replace them with 400 to give you 24,000 RPM max.

Respond:

Other Possible Solutions to this Question

Get Help with:
This Product
Orders
Tech Support
Sales
This Product
Order Query
Tech Support
Sales
Not logged in. Log In Register
Track Order(s)
View Order(s)
I Want to Schecule a One-On-One Paid Tech Support Session
Book an Appointment Pertaining to a BuildYourCNC Product (Free)
Ask a Quesion Below (Free):
Book an Appointment Pertaining Other Equipment ($60/half hour)
Book an Immedite Appointment Pertaining Other Equipment ($120/half hour)
Ask a Quesion Below (Free):
Waiting for response... I may not answer immediately, but I was notified on my cellular phone so my response is forthcoming. If I don't respond immediately, you can always go to the [My Account] page to see all of our chats at any time.