Question #: 2260

Question: Can you provide setting for the VFD setting for 110v US, 1.5kw 220v spindle?

Current Solution

The configuration settings for our VFD's are these: VFD Setup:
Change PD001 to '0' (source of run commands)
Change PD003 to 300 (main frequency - Hz)
Change PD004 to 300 (base frequency - Hz)
Change PD005 to 400 (max operating frequency - Hz)
Change PD006 to 2.5 (intermediate frequency - Hz)
Change PD008 to 220 (max voltage - V)
Change PD009 to 15 (intermediate voltage - V)
Change PD010 to 8 (minimum voltage - V)
Change PD011 to 100 (frequency lower limit - Hz)
Change PD142 to 7 (rated motor current - Amps)
Change PD143 to 2 (motor pole number)
Change PD144 to 3000 (rated motor revolution)
For further info please refer to (https://www.buildyourcnc.com/item/spindle-inverter-2!2kw-spindle-novfd#prettyPhoto) for wiring and other specifications.

Respond:

Other Possible Solutions to this Question

  • Can you provide configuration setting for the 110v Huangyang VFD and 1.5 kw spindle?

    The configuration settings for our VFD's are these: VFD Setup:
    Change PD001 to '0' (source of run commands)
    Change PD003 to 300 (main frequency - Hz)
    Change PD004 to 300 (base frequency - Hz)
    Change PD005 to 400 (max operating frequency - Hz)
    Change PD006 to 2.5 (intermediate frequency - Hz)
    Change PD008 to 220 (max voltage - V)
    Change PD009 to 15 (intermediate voltage - V)
    Change PD010 to 8 (minimum voltage - V)
    Change PD011 to 100 (frequency lower limit - Hz)
    Change PD142 to 7 (rated motor current - Amps)
    Change PD143 to 2 (motor pole number)
    Change PD144 to 3000 (rated motor revolution)
    For further info please refer to (https://www.buildyourcnc.com/item/spindle-inverter-2!2kw-spindle-novfd#prettyPhoto) for wiring and other specifications.

    Click the link to add information to this solution:
    Can you provide configuration setting for the 110v Huangyang VFD and 1.5 kw spindle?

  • What length of wire do you recommend for the black toe (2'x4') between the spindle and VFD?

    The length of the cable from the VFD (Variable Frequency Drive) to the actual spindle should be about the same as the z-axis cable from the z-axis motor to the z-axis driver which is recommended at 11 feet. This is locating the VFD about at the midpoint of the machine.

    Click the link to add information to this solution:
    What length of wire do you recommend for the black toe (2'x4') between the spindle and VFD?

  • What are the model numbers for your 2.2kw 110v and 220v VFDs? Or can you share a link to their documentation?

    Documentation for Parameter setup is included with VFD purchase. For spindle wiring and programming, please refer to the product pages for the spindles or VFDs (or the combo kit) and scroll down to instructions. For further assistance you can contact customerservice@buildyourcnc.com

    Click the link to add information to this solution:
    What are the model numbers for your 2.2kw 110v and 220v VFDs? Or can you share a link to their documentation?

  • CAN YOU RECOMMEND WHICH CNC MACHINE TO GO WITH FOR CUTTING MELAMINE AND MAKING KITCHEN DOORS FROM MDF. ALSO DO PROVIDE TRAINING ON OPERATING SETTING UP SHOP PRODUCTION USE? THANKS

    All of our CNC machines can cut melamine. If your application (kitchen doors) requires large cutting area, then I would recommend the following machines:

    - greenBull 4x (4'x8'), 5x (5'x10') or 6x (6'x 12')

    - greenLean 4'x8' vertically oriented CNC machine

    - Or our Fabricator Pro 4'x8' metal CNC machine

    Click the link to add information to this solution:
    CAN YOU RECOMMEND WHICH CNC MACHINE TO GO WITH FOR CUTTING MELAMINE AND MAKING KITCHEN DOORS FROM MDF. ALSO DO PROVIDE TRAINING ON OPERATING SETTING UP SHOP PRODUCTION USE? THANKS

  • What size of wire do you use to connect the VFD to the spindle?

    The type of wire that should be used between the spindle and the VFD (Variable Frequency Driver also called the inverter) should be of stranded type and we use between 18 and 16 AWG.

    The total current is divided among the three coil wires, therefor a wire gauge of 16 should be sufficient.

    Currently we use 20AWG 4 conductor.

    Additional Information:


    Additional Information:



    Additional Information:



    Additional Information:

    Click the link to add information to this solution:
    What size of wire do you use to connect the VFD to the spindle?

  • How do you connect the spindle VFD to the parallel breakout board

    The parallel board contains a relay that is connected to pin #16. You can use this relay as the start/stop by connecting the relay to the FOR and it's related digital GND pin on the VFD.

    Additional Information:


    Additional Information:


    Additional Information:


    Additional Information:

    Click the link to add information to this solution:
    How do you connect the spindle VFD to the parallel breakout board

  • What brand is the 2.2 kW spindle? Same for the VFD. Thanks.

    Spindles are generally covered up to 1 year after date of purchase. We do not repair them in house, but we do work with our manufacturer to replace defective units. Generally if you have a defective unit covered under warranty, we will issue a replacement.

    Click the link to add information to this solution:
    What brand is the 2.2 kW spindle? Same for the VFD. Thanks.

  • 2.2kW Spindle with 110V Inverter, can I get a collet for 1/2 router bits for this spindle

    Absolutely. You can have 1/2" collets used in 2.2kW spindles.

    Here is a link for the ER-20 1/2"ID Collet:
    https://www.buildyourcnc.com/item/spindle-collet-!5-er20-spindle-collet

    Click the link to add information to this solution:
    2.2kW Spindle with 110V Inverter, can I get a collet for 1/2 router bits for this spindle

  • Are there any other manuals for the VFD that comes with the 2.2kw spindle?

    We have manuals for the VFD rather than the spindles. Can you specify what issue you may be having so we can help you better?

    Additional Information:
    I am having trouble wiring the VFD. (From the wall outlet to the VFD) I think the manual or setup guide on your website is wrong. The two diagrams show two different sets of terminals on the page.

    Also, do you have a video or other documentation on programming the VFD? Your videos and documentation looks like it only covers the 1.2kw version. Are the two different spindles from different manufacturers?

    Click the link to add information to this solution:
    Are there any other manuals for the VFD that comes with the 2.2kw spindle?

  • I ordered a 1.5kW 110V Spindle on 11/28. It still shows "processing." Is this on backorder? Any ETA I can expect?

    Yes, we were waiting for the VFDs and Spindles to arrive from China. We emailed you the tracking numbers today.

    Click the link to add information to this solution:
    I ordered a 1.5kW 110V Spindle on 11/28. It still shows "processing." Is this on backorder? Any ETA I can expect?

  • HOW DO YOU SETUP THE SPINDLE INVERTER VFD?

    Change PD001 Source of Run Commands to '1'
    Change PD005 Max operating frequency to 400hz
    Change PD004 base frequency to 400hz
    Change PD003 Main frequency to 400hz
    Change PD006 Intermediate frequency to 2.5
    Change PD008 max voltage to 220v
    Change PD009 Intermediate voltage to 15v
    Change PD010 Min voltage to 8
    Change PD011 frequency lower limit to >100hz (120hz to start)
    Change PD142 7 Amps
    Change PD143 2
    Change PD144 3000

    Note: PD001 had to be changed back to 0 to allow for keypad control.
    Note2: I had to reverse U and V to get the spindle to go forward in FWD. (reverse any two wires, u&v or w&v for example)

    Additional Information:

    Click the link to add information to this solution:
    HOW DO YOU SETUP THE SPINDLE INVERTER VFD?

  • HOW DO YOU HOOK UP THE VFD TO SPINDLE?

    U - Pin1
    V - Pin2
    W - Pin3
    Pin4 Dead

    Additional Information:
    My home made cnc is a big problem with my NC connection. When in start my spindle it will be gone wrong. It will be limith switch problem anytime. Need help thanks.

    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:



    Additional Information:

    Click the link to add information to this solution:
    HOW DO YOU HOOK UP THE VFD TO SPINDLE?

  • Good morning, I would like to know if the strength of the 2.2kw spindle is weaker when using the 110V version of the VFD. Does it have the same power as the 220V version VFD?

    The 2.2kW spindle will have the same amount of torque and strength using either the 110V or the 220V inverter. Nothing will significantly change in either application since the 110V inverter has a small step up transformer which will increase the voltage from 110V to 220V to run the spindle efficiently.

    Additional Information:
    I'd like confirmation on this -- isn't there a cost in efficiency to having the 110v step up to 220v?

    Additional Information:
    Thank you so very much for explaining this!!! I truly appreciate your help! Tricia

    Additional Information:
    Thank you so very much for explaining this!!! I truly appreciate your help! Tricia

    Additional Information:
    Thank you so very much for explaining this!!! I truly appreciate your help! Tricia

    Additional Information:
    Thank you so very much for explaining this!!! I truly appreciate your help! Tricia

    Additional Information:
    Thank you so very much for explaining this!!! I truly appreciate your help! Tricia

    Click the link to add information to this solution:
    Good morning, I would like to know if the strength of the 2.2kw spindle is weaker when using the 110V version of the VFD. Does it have the same power as the 220V version VFD?

  • It is possible to control externally the 1.5kW Inverter (VFD) (220 Volt) with PWM so i can control the spindle rotation? Do you have the documentation? Thank you

    Our spindle VFD's, have a multitude of different connectors that can be used for different operations. There is a manual that comes with each VFD, and you can refer to page 11 for different functions and descriptions.

    We currently have a PWM, working with our machine, however it is connected via USB, and setup through Mach 3.
    Also if you may have misplaced or lost the manual here is a link to the pdf:

    (https://www.google.com/url?sa=t&rct=j&q=&esrc=s&source=web&cd=1&cad=rja&uact=8&ved=0CCAQFjAAahUKEwibxaaIndTHAhXQlogKHZVyDFE&url=http%3A%2F%2Fwww.c-n-c.cz%2Fdownload%2Ffile.php%3Fid%3D42252&ei=_cHkVdvSC9CtogSV5bGIBQ&usg=AFQjCNHTQcxs-KhJkvkhMdxVFPzkoYJtsA&sig2=JAcZawTGMuC-t4wmn1z-rA)

    Click the link to add information to this solution:
    It is possible to control externally the 1.5kW Inverter (VFD) (220 Volt) with PWM so i can control the spindle rotation? Do you have the documentation? Thank you

  • What are the configuration settings for VFD for Spindle 1.5kW 110V. The search settings have a link for a 2.2kw spindle so I'm afraid they are the wrong ones and I don't want to fry the spindle. My VFD is an Huanyang HY01D511B.

    Did you get a manual for your VFD? Where did you purchase the VFD and spindle?

    Additional Information:
    I bought the VFD through Amazon with a similar spindle that you sell. The VFD came with a manual but unfortunately the spindle had all the model number and specs scratched off of it. In an attempt to set it up, I fried the spindle. I have complained to the vendor and to Amazon but have received no solution. If your spindle arrives with proper documentation I probably can set it up myself.

    Click the link to add information to this solution:
    What are the configuration settings for VFD for Spindle 1.5kW 110V. The search settings have a link for a 2.2kw spindle so I'm afraid they are the wrong ones and I don't want to fry the spindle. My VFD is an Huanyang HY01D511B.

  • How can we check our 1.5kw spindle. we get a dL error after we start to cut. it spins up fine. We checked IGBTs in the VFD and they're not shorted. We suspect intermittent short INSIDE the spindle. What do you think?

    dL usually stand for a short that is occurring within the spindle or spindle wiring. I would recheck the wiring going from the VFD to the spindle, as well as the terminal on the spindle where there should've been some soldering required. We usually tend to either heat shrink or use electrical tape to cover the terminals so no contact or arching can be present.

    Also depending on the VFD you have please adjust the setting pd008, to the voltage that is required (110V/220V).

    If the issue proceeds please contact use at customerservice@buildyourcnc.com, for further assistance or replacement.

    Click the link to add information to this solution:
    How can we check our 1.5kw spindle. we get a dL error after we start to cut. it spins up fine. We checked IGBTs in the VFD and they're not shorted. We suspect intermittent short INSIDE the spindle. What do you think?

  • I'VE BUFFERED A PWM SIGNAL TO 0-10V ANALOG AND I WOULD LIKE USE THAT RUN YOUR 110V 2.2KW SPINDLE VFD. COULD YOU PLEASE DETAIL THE CORRECT WIRING VFD SETTINGS GET WORKING?

    This will depend on the VFD you have to identify the correct terminal. The terminal on the VFD will be labeled AI1 typically (Analog Input #1). You will also need to make sure to complete the PWM circuit using the GND terminal on the VFD.

    Additional Information:
    I have wired my 0-10V signal to the AI1 and GND terminals as suggested. I have also set the PD-01 and PD-02 settings to 1. Still nothing. Is there something else that I am missing?

    Additional Information:
    Thanks for the information. Can you let me know the model of the VFD that you have?

    Additional Information:
    VFD Model # YL600-2S-2K20

    Additional Information:
    Thanks. I will check our resources and documentation to see if there is another programming setting that needs to be changed.

    Additional Information:
    Does your VFD have a VI terminal?

    Additional Information:
    No, it does not. The terminals for this VFD are as follows (seperated by dashes "-").

    10V-AI1-AO2-PLC-DI5-DI3-DI1-COM
    AI2-GND-AO1-DI6-DI4-DI2-FM-24V

    Additional Information:
    Do you have a PD070 parameter?

    PD070 is the main Analog Input parameter.

    The options for that parameter is:
    0: 0-10V
    1: 0-5V
    2: 0-20mA
    3: 4-20mA
    4: 0-10V (4-20mA Stacked)
    5: XIA
    6: (VI+XIA)/2
    7: (3VA+XIA)/4
    8: (XIA_XIB)/2
    9: Max (XIA, XIB)
    10: Min (XIA, XIB)


    Additional Information:
    There is a PD-00 thru PD-09. PD-07 is currently set to 0.

    Additional Information:
    It appears that the manual I’m using “Titled YL600” is not the same as your unit. I will check our manuals and find the one that has only PD-00 to PD-09.

    Additional Information:
    For that VFD, the parameters are P0. The 0 may look like a D on the display.

    The parameters that need to be changed for the AI1 to work (Brackets [] around the correct selection):

    P0-01: First Motor Control Mode
    - 0: Sensorless Vector Control
    - 1: Flux Vector Control (FVC)
    - [2]: V/F Control

    P0-02: Options of Command Source
    - 0: Operation Panel Command Channel (LED will be off)
    - [1]: Terminal Command Channel (LED will be on)
    - 2: Communication Command Channel (LED will flicker)

    P0-03: Options of Principle Frequency Source X
    - 0: Digital Setting (Preset Frequency P0-08, UP/DOWN modifiable, no power-down memory)
    - 1: Digital Setting (Preset Frequency P0-08, UP/DOWN modifiable, with power-down memory)
    - [2]: AI1
    - 3: AI2
    - 4: AI3
    - 5: Pulse Setting (DI5)
    - 6: Multi Speed Instruction
    - 7: Simple PLC
    - 8: PID (Proportional Integral Derivative Control)
    - 9: Communication Given

    P0-11: Upper Limit Frequency Source
    - 0: P0-12 (Make sure the P0-12 parameter has the correct max frequency if used)
    - [1]: AI1
    - 2: AI2
    - 3: AI3
    - 4: Pulse Setting
    - 5: Communication Given

    P0-27: Command Source Bundle with Frequency Sources
    Single Digit: Options of Operation Panel Command Bundle with Frequency Sources
    - 0: No Bundling
    - 1: Digital Setting Frequency
    - [2]: AI1
    - 3: AI2
    - 4: AI3
    - 5: Pulse Setting (DI5)
    - 6: Multi Speed Instruction
    - 7: Simple PLC
    - 8: PID
    - 9: Communication Given
    Double Digit: Options of Terminal Command Bundle with Frequency Sources
    Hundred Place: Options of Communication Command Bundle with Frequency Sources
    Kilobit: Options of Automatic Operation Bundle with Frequency Sources

    P2-09: Upper Limit Source of Lower Torque Under Speed Control Mode
    - 0: Function Code P2-10 Setting
    - [1]: AI1
    - 2: AI2
    - 3: AI3
    - 4: Pulse Setting
    - 5: Communication Given
    - 6: MIN (Al1, Al2)
    - 7: MAX (Al1, Al2)
    - Maximum range for options 1-7, accords with P2-10

    If you elect to use a different AI#, then configure the parameters (P0-03, P0-11, P0-27 and P2-09) accordingly.

    Click the link to add information to this solution:
    I'VE BUFFERED A PWM SIGNAL TO 0-10V ANALOG AND I WOULD LIKE USE THAT RUN YOUR 110V 2.2KW SPINDLE VFD. COULD YOU PLEASE DETAIL THE CORRECT WIRING VFD SETTINGS GET WORKING?

  • I HAVE THE REDFLY SYSTEM AND A 2.2KW SPINDLE - 110V HOW DO CONNECT SPINDAL?

    It is not necessary to connect the spindle VFD (Variable Frequency Drive also called an Inverter) to the computer or CNC motion electronics. The VFD can be controlled independently using the control panel on the VFD. The control panel has the ability to control all aspects of the spindle including Speed, Torque, limits, etc. However, you can connect the VFD to the computer so the CNC control program can control the spindle during the CNC Machine operation. You will need to connect the VFD to the computer via a serial conection (in this case, it is the RS-485 protocol).

    The following are instructions on how to connect the VFD to Mach3 via this RS-485 serial connection.

    The first thing you will need is the dynamic link library to pair with mach3 called the Huanyang VFD Mach3 PlugIn. You can find this file at the mach3 support forum here: http://www.machsupport.com/forum/index.php/topic,14182.0.html

    You will also need to download the Microsoft .net 3.5 framework and install it: https://www.microsoft.com/en-us/download/details.aspx?id=21

    Follow the pdf that comes with the library file, but here is a synopsis of what you need to do (I also added a lot more information that may be useful during this process as the manual does not cover the main connections that need to be done):

    You will need to program your VFD so that it knows how to communicate with mach3 and the computer (go into the programming mode of the VFD and change these parameters):
    - PD001 - value 2 - Enables with communication aspect of the VFD
    - PD002 - value 2 - Enables frequency control from the communcations port
    - PD163 - value 1 - VFD address
    - PD164 - value 1 - Baud rate of 9600 (speed of the communication)
    - PD165 - value 3 - 8N1 RTU - 8 bits (that's the size of the word that gets communicated), N (No parity or no error checking) and 1 (1 stop bit)

    Copy the dll file to the PlugIns folder of mach3.

    Connect the RX and TX lines to your computer. There are a couple ways you can do this, but the recommended way would be to use an FTDI USB device which converts a USB to a serial com port. The device will have Rx and Tx connectors to connect to the VFD terminals with the same labels. This method is recommended since serial ports are not as common in computers these days.

    Next, you will need to configure mach3 to use the plugin library. Start mach3 and click on Menu -> config ->Config Plugins. Enable the new plugin by clicking on the red cross on the left column next to the plug in. Restart mach3 after doing this.

    No you need to configure mach3 to use the HuanyangVFD plugin. Go to the ports & pins configuration and select the spindle setup tab. Make sure that the Disable Spindle Relays checkbox is unchecked. We don't want mach3 to output a signal for a relay since the spindle will start up and turn off within the VFD and not from an external relay.

    Next, go to the HuanyangVFD settings by clicking on Menu -> plugin control -> HuanyangVFD. Set the parameters to the same settings you put into the VFD programming. The com port will be shown as new hardward when you plug in the USB FTDI device. A little bubble will be displayed at the bottom right where it will notify you that a new device is being installed (be patient while windows assigns a com port). Alternatively, you can use the windows device manager to see which port was set for the new USB FTDI device). You may need to restart mach3 several times until you get the correct information displayed in the PD001 and PD002 fields. When the com port is correct and the other parameters, like baud and VFD address is the same as you entered in the programming, then the PD001 and PD002 will show the number 2, otherwise, a 99 will appear which means that communication was not successful.

    You can now control the on/off and RPM of the spindle using the RS485 communication between mach3 and the VFD.

    Additional Information:
    The question was how to connect the spindle to the redfy. I did not receive a VFD.
    I have the redFly system and a 2.2kW Spindle - 110V how do i connect the spindle?

    Additional Information:
    If you received a spindle without a VFD, please contact us asap. Our spindle will not work without a VFD.

    Additional Information:
    Hi, how is this setup in mach4?

    Click the link to add information to this solution:
    I HAVE THE REDFLY SYSTEM AND A 2.2KW SPINDLE - 110V HOW DO CONNECT SPINDAL?

  • How do I conect the VFD of the spindle to the RS485 connections

    It is not necessary to connect the spindle VFD (Variable Frequency Drive also called an Inverter) to the computer or CNC motion electronics. The VFD can be controlled independently using the control panel on the VFD. The control panel has the ability to control all aspects of the spindle including Speed, Torque, limits, etc. However, you can connect the VFD to the computer so the CNC control program can control the spindle during the CNC Machine operation. You will need to connect the VFD to the computer via a serial conection (in this case, it is the RS-485 protocol).

    The following are instructions on how to connect the VFD to Mach3 via this RS-485 serial connection.

    The first thing you will need is the dynamic link library to pair with mach3 called the Huanyang VFD Mach3 PlugIn. You can find this file at the mach3 support forum here: http://www.machsupport.com/forum/index.php/topic,14182.0.html

    You will also need to download the Microsoft .net 3.5 framework and install it: https://www.microsoft.com/en-us/download/details.aspx?id=21

    Follow the pdf that comes with the library file, but here is a synopsis of what you need to do (I also added a lot more information that may be useful during this process as the manual does not cover the main connections that need to be done):

    You will need to program your VFD so that it knows how to communicate with mach3 and the computer (go into the programming mode of the VFD and change these parameters):
    - PD001 - value 2 - Enables with communication aspect of the VFD
    - PD002 - value 2 - Enables frequency control from the communcations port
    - PD163 - value 1 - VFD address
    - PD164 - value 1 - Baud rate of 9600 (speed of the communication)
    - PD165 - value 3 - 8N1 RTU - 8 bits (that's the size of the word that gets communicated), N (No parity or no error checking) and 1 (1 stop bit)

    Copy the dll file to the PlugIns folder of mach3.

    Connect the RX and TX lines to your computer. There are a couple ways you can do this, but the recommended way would be to use an FTDI USB device which converts a USB to a serial com port. The device will have Rx and Tx connectors to connect to the VFD terminals with the same labels. This method is recommended since serial ports are not as common in computers these days.

    Next, you will need to configure mach3 to use the plugin library. Start mach3 and click on Menu -> config ->Config Plugins. Enable the new plugin by clicking on the red cross on the left column next to the plug in. Restart mach3 after doing this.

    No you need to configure mach3 to use the HuanyangVFD plugin. Go to the ports & pins configuration and select the spindle setup tab. Make sure that the Disable Spindle Relays checkbox is unchecked. We don't want mach3 to output a signal for a relay since the spindle will start up and turn off within the VFD and not from an external relay.

    Next, go to the HuanyangVFD settings by clicking on Menu -> plugin control -> HuanyangVFD. Set the parameters to the same settings you put into the VFD programming. The com port will be shown as new hardward when you plug in the USB FTDI device. A little bubble will be displayed at the bottom right where it will notify you that a new device is being installed (be patient while windows assigns a com port). Alternatively, you can use the windows device manager to see which port was set for the new USB FTDI device). You may need to restart mach3 several times until you get the correct information displayed in the PD001 and PD002 fields. When the com port is correct and the other parameters, like baud and VFD address is the same as you entered in the programming, then the PD001 and PD002 will show the number 2, otherwise, a 99 will appear which means that communication was not successful.

    You can now control the on/off and RPM of the spindle using the RS485 communication between mach3 and the VFD.

    Additional Information:
    The question was how to connect the spindle to the redfy. I did not receive a VFD.
    I have the redFly system and a 2.2kW Spindle - 110V how do i connect the spindle?

    Additional Information:
    If you received a spindle without a VFD, please contact us asap. Our spindle will not work without a VFD.

    Additional Information:
    Hi, how is this setup in mach4?

    Click the link to add information to this solution:
    How do I conect the VFD of the spindle to the RS485 connections

Get Help with:
This Product
Orders
Tech Support
Sales
This Product
Order Query
Tech Support
Sales
Not logged in. Log In Register
Track Order(s)
View Order(s)
I Want to Schecule a One-On-One Paid Tech Support Session
Book an Appointment Pertaining to a BuildYourCNC Product (Free)
Ask a Quesion Below (Free):
Book an Appointment Pertaining Other Equipment ($60/half hour)
Book an Immedite Appointment Pertaining Other Equipment ($120/half hour)
Ask a Quesion Below (Free):
Waiting for response... I may not answer immediately, but I was notified on my cellular phone so my response is forthcoming. If I don't respond immediately, you can always go to the [My Account] page to see all of our chats at any time.