Question #: 3430

Question: I purchased the 4.0kw spindle and VFD a while back, and have just installed a PMDX-107 controller... do you have any examples of the wiring connections for the SL-240EE to PMDX-107?

Current Solution

If you want speed control, it is recommended to use the RS-485 connection on the VFD and use the control program such as Mach3 to communication serially with the VFD using this RS-485 connection.

If you would rather use a controller such as the PMDX-107 to simulate the effect of a potentiometer using the Aref, Aout and Agnd and the Rev/Dir and Fwd/Run terminals to control operation and direction, you can connect those to the VFD.

PMDX-107 Aout connects to the VI (analog voltage in). This is like the wiper on a potentiometer.
PMDX-107 Agnd connects to the ACM terminal on the VFD for Analog common.
PMDX-107 COM connects to DCM terminal on the VFD for Digital common.
PMDX-107 Fwd/Run connects to the FOR terminal on the VFD for Forward.
PMDX-107 Rev/Dir connects to the REV terminal on the VFD for Reverse.

Refer to your PMDX-107 manual to correctly configure your dip switch settings and make sure to calibrate (tweak) the speed control using the trimmer next to the terminals on the PMDX-107.

Respond:

Other Possible Solutions to this Question

Get Help with:
This Product
Orders
Tech Support
Sales
This Product
Order Query
Tech Support
Sales
Not logged in. Log In Register
Track Order(s)
View Order(s)
I Want to Schecule a One-On-One Paid Tech Support Session
Book an Appointment Pertaining to a BuildYourCNC Product (Free)
Ask a Quesion Below (Free):
Book an Appointment Pertaining Other Equipment ($60/half hour)
Book an Immedite Appointment Pertaining Other Equipment ($120/half hour)
Ask a Quesion Below (Free):
Waiting for response... I may not answer immediately, but I was notified on my cellular phone so my response is forthcoming. If I don't respond immediately, you can always go to the [My Account] page to see all of our chats at any time.