Question #: 14529

Question: Why does my VFD show the error er.04?

Current Solution

The Er.04 (if you are using the YL VFD), generally refers to the ramping up and ramping down of the spindle, but it can be a result of a short circuit between the VFD and the spindle. You can increase the time the spindle accelerates (ramps up to the set rpm/frequency).

Respond:

Other Possible Solutions to this Question

  • what does the error code on my vfd mean?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Click the link to respond:
    what does the error code on my vfd mean?

  • my vfd is showing an error code

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Click the link to respond:
    my vfd is showing an error code

  • My VFD/inverter is showing an er.04 er 04 on the display when the spindle starts spinning

    The Er.04 (if you are using the YL VFD), generally refers to the ramping up and ramping down of the spindle, but it can be a result of a short circuit between the VFD and the spindle. You can increase the time the spindle accelerates (ramps up to the set rpm/frequency).

    Click the link to respond:
    My VFD/inverter is showing an er.04 er 04 on the display when the spindle starts spinning

  • what does it mean when my spindle VFD inverter shows OC-2?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Click the link to respond:
    what does it mean when my spindle VFD inverter shows OC-2?

  • My VFD has started to dL error at startup, what could be the issue?

    The DL error usually means that there is a short in the wiring going from the VFD to the Spindle. First remove the spindle connection and run the VFD. If "DL" does not appear then this means the short is on the spindle itself. Remember to double check your wiring and to use heat shrink on the soldering points to prevent any shorts or arcing between the points.

    Additional Information:


    Additional Information:
    My drive showing dp when it start

    Click the link to respond:
    My VFD has started to dL error at startup, what could be the issue?

  • what are the vfd spindle error codes

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Click the link to respond:
    what are the vfd spindle error codes

  • My spindle inverter is showing an E.o.l.A error.

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Click the link to respond:
    My spindle inverter is showing an E.o.l.A error.

  • why does the parallel port breakout board have usb port?

    The parallel breakout board contains a USB port to power the board. Through the USB port, the computer delivers 5v of stable power to the parallel breakout board, but doe not provide any communication as would normally be associated with USB connectivity.

    The reason we elected to use the USB port to provide power is to remove the need for an external 5v wall adapter.

    Click the link to respond:
    why does the parallel port breakout board have usb port?

  • how much does the 2.2kW spindle and the VFD weigh together?

    The weight of the 2.2kW spindle without the VFD (variable frequency drive or inverter) is 11 lbs or 5 kg.

    The 2.2kW spindle with the VFD is 15 lbs or 6.8 kg.

    Click the link to respond:
    how much does the 2.2kW spindle and the VFD weigh together?

  • vfd error 4 code, how do I fix this?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Click the link to respond:
    vfd error 4 code, how do I fix this?

  • Can we get a VFD Error Code listing?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Click the link to respond:
    Can we get a VFD Error Code listing?

  • vfd and spindle error codes listing

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Click the link to respond:
    vfd and spindle error codes listing

  • My router does not fit in the mount supplied in the kit

    If you are using a router that will not fit into the router mount, it is best to have the mount requested from us. The mounts were designed with the appropriate thickness of material for structural purposes and to maintain this structure under load.

    Click the link to respond:
    My router does not fit in the mount supplied in the kit

  • My router does not fit in the mount supplied in the kit

    If you are using a router that will not fit into the router mount, it is best to have the mount requested from us. The mounts were designed with the appropriate thickness of material for structural purposes and to maintain this structure under load.

    Click the link to respond:
    My router does not fit in the mount supplied in the kit

  • Will your 2.5 KW spindle work with my Hitachi WJ200-022SF VFD and does it have a thermal couple temp output?

    From reading on the Hitachi WJ200-022SF VFD, it seems as it will work just fine with this VFD. However since we have not tried this cross match, I would carefully take each connection and setting into great consideration and detail on both the Hitachi recommendations for setup, as well as our spindles recommended setup.
    Our spindles do not have a thermal couple temperature output.

    Click the link to respond:
    Will your 2.5 KW spindle work with my Hitachi WJ200-022SF VFD and does it have a thermal couple temp output?

  • the pins on the 110 VFD are marked different than the one shown in picture?

    There is another image on the spindle page here that shows another type of wiring using the R, T and E terminals for power. The image is one of the clickable main images on that page:

    https://www.buildyourcnc.com/item/spindle-inverter-2!2kw-spindle-novfd

    Additional Information:
    Here is a link to the image directly:

    https://www.buildyourcnc.com/images/SpindleWiring-800.JPG

    And here is the link to the alternate diagram:

    https://www.buildyourcnc.com/images/NewSpindleDiagram-800.JPG

    Click the link to respond:
    the pins on the 110 VFD are marked different than the one shown in picture?

  • why did the laser on my blacktooth slowly lose it's power during a cut? Currently does not fire. X/Y jogs fine.

    There could have been a small, slow leak in the tube, releasing the CO2 gas. The power supply could have also suffered from an electrical issue.

    Click the link to respond:
    why did the laser on my blacktooth slowly lose it's power during a cut? Currently does not fire. X/Y jogs fine.

  • Is there a way to use Mach4 to control my VFD?

    The best way to determine how to control your VFD using Mach4 is to read the MAch4 manual found here:
    http://www.machsupport.com/wp-content/uploads/2014/05/Mach4%20Installation%20Manual.pdf

    You will find that there a a few ways to control the spindle/VFD on your CNC machine or CNC Router.
    - The first and easiest is to have your VFD's power controlled by a relay. This will allow your spindle to have on/off control through Mach4 with an output pin.
    - The second is to have a controller output a DAC voltage between 0-10 volts to control speed on the VFD/Spindle. There is a termial on the VFD to receive this signal line. The controller will also have an output that outputs a high or low and that can control the on/off on the VFD.
    - The third, and more difficult of the three methods is to use a USB to Serial adapter (USB to USART or RS-485). The Computer plugs into the adapter using a USB cable and the adapter uses the RX/TX to connect to the VFD's terminals for communication. This will provide a great amount of control. Mach4 will need a plug-in to make this option work.

    Click the link to respond:
    Is there a way to use Mach4 to control my VFD?

  • The limit switches keep triggering or erroring.

    Are you using shielded wire? If so, take the shield to ground. If there are any other wires in the cable that is not being used, ground those as well. The customer can also try moving the cables as far away as possible from the motor wires and motors.

    Additional Information:

    Click the link to respond:
    The limit switches keep triggering or erroring.