[ Log In ]
[ Register ]

Question #: 3628

Question: What gauge wire between the VFD and the 2.2K spindle? The spindle connection posts are very tiny, equivalent to 18 gauge, but that seems too small. What do you use?

Current Solution

The type of wire that should be used between the spindle and the VFD (Variable Frequency Driver also called the inverter) should be of stranded type and we use between 18 and 16 AWG.

The total current is divided among the three coil wires, therefor a wire gauge of 16 should be sufficient.

Currently we use 20AWG 4 conductor.

Additional Information:


Additional Information:



Additional Information:



Additional Information:

Respond:

Other Possible Solutions to this Question

  • What length of wire do you recommend for the black toe (2'x4') between the spindle and VFD?

    The length of the cable from the VFD (Variable Frequency Drive) to the actual spindle should be about the same as the z-axis cable from the z-axis motor to the z-axis driver which is recommended at 11 feet. This is locating the VFD about at the midpoint of the machine.

    Click the link to add information to this solution:
    What length of wire do you recommend for the black toe (2'x4') between the spindle and VFD?

  • I'VE BUFFERED A PWM SIGNAL TO 0-10V ANALOG AND I WOULD LIKE USE THAT RUN YOUR 110V 2.2KW SPINDLE VFD. COULD YOU PLEASE DETAIL THE CORRECT WIRING VFD SETTINGS GET WORKING?

    This will depend on the VFD you have to identify the correct terminal. The terminal on the VFD will be labeled AI1 typically (Analog Input #1). You will also need to make sure to complete the PWM circuit using the GND terminal on the VFD.

    Additional Information:
    I have wired my 0-10V signal to the AI1 and GND terminals as suggested. I have also set the PD-01 and PD-02 settings to 1. Still nothing. Is there something else that I am missing?

    Additional Information:
    Thanks for the information. Can you let me know the model of the VFD that you have?

    Additional Information:
    VFD Model # YL600-2S-2K20

    Additional Information:
    Thanks. I will check our resources and documentation to see if there is another programming setting that needs to be changed.

    Additional Information:
    Does your VFD have a VI terminal?

    Additional Information:
    No, it does not. The terminals for this VFD are as follows (seperated by dashes "-").

    10V-AI1-AO2-PLC-DI5-DI3-DI1-COM
    AI2-GND-AO1-DI6-DI4-DI2-FM-24V

    Additional Information:
    Do you have a PD070 parameter?

    PD070 is the main Analog Input parameter.

    The options for that parameter is:
    0: 0-10V
    1: 0-5V
    2: 0-20mA
    3: 4-20mA
    4: 0-10V (4-20mA Stacked)
    5: XIA
    6: (VI+XIA)/2
    7: (3VA+XIA)/4
    8: (XIA_XIB)/2
    9: Max (XIA, XIB)
    10: Min (XIA, XIB)


    Additional Information:
    There is a PD-00 thru PD-09. PD-07 is currently set to 0.

    Additional Information:
    It appears that the manual I’m using “Titled YL600” is not the same as your unit. I will check our manuals and find the one that has only PD-00 to PD-09.

    Additional Information:
    For that VFD, the parameters are P0. The 0 may look like a D on the display.

    The parameters that need to be changed for the AI1 to work (Brackets [] around the correct selection):

    P0-01: First Motor Control Mode
    - 0: Sensorless Vector Control
    - 1: Flux Vector Control (FVC)
    - [2]: V/F Control

    P0-02: Options of Command Source
    - 0: Operation Panel Command Channel (LED will be off)
    - [1]: Terminal Command Channel (LED will be on)
    - 2: Communication Command Channel (LED will flicker)

    P0-03: Options of Principle Frequency Source X
    - 0: Digital Setting (Preset Frequency P0-08, UP/DOWN modifiable, no power-down memory)
    - 1: Digital Setting (Preset Frequency P0-08, UP/DOWN modifiable, with power-down memory)
    - [2]: AI1
    - 3: AI2
    - 4: AI3
    - 5: Pulse Setting (DI5)
    - 6: Multi Speed Instruction
    - 7: Simple PLC
    - 8: PID (Proportional Integral Derivative Control)
    - 9: Communication Given

    P0-11: Upper Limit Frequency Source
    - 0: P0-12 (Make sure the P0-12 parameter has the correct max frequency if used)
    - [1]: AI1
    - 2: AI2
    - 3: AI3
    - 4: Pulse Setting
    - 5: Communication Given

    P0-27: Command Source Bundle with Frequency Sources
    Single Digit: Options of Operation Panel Command Bundle with Frequency Sources
    - 0: No Bundling
    - 1: Digital Setting Frequency
    - [2]: AI1
    - 3: AI2
    - 4: AI3
    - 5: Pulse Setting (DI5)
    - 6: Multi Speed Instruction
    - 7: Simple PLC
    - 8: PID
    - 9: Communication Given
    Double Digit: Options of Terminal Command Bundle with Frequency Sources
    Hundred Place: Options of Communication Command Bundle with Frequency Sources
    Kilobit: Options of Automatic Operation Bundle with Frequency Sources

    P2-09: Upper Limit Source of Lower Torque Under Speed Control Mode
    - 0: Function Code P2-10 Setting
    - [1]: AI1
    - 2: AI2
    - 3: AI3
    - 4: Pulse Setting
    - 5: Communication Given
    - 6: MIN (Al1, Al2)
    - 7: MAX (Al1, Al2)
    - Maximum range for options 1-7, accords with P2-10

    If you elect to use a different AI#, then configure the parameters (P0-03, P0-11, P0-27 and P2-09) accordingly.

    Click the link to add information to this solution:
    I'VE BUFFERED A PWM SIGNAL TO 0-10V ANALOG AND I WOULD LIKE USE THAT RUN YOUR 110V 2.2KW SPINDLE VFD. COULD YOU PLEASE DETAIL THE CORRECT WIRING VFD SETTINGS GET WORKING?

  • What size of wire do you use to connect the VFD to the spindle?

    The type of wire that should be used between the spindle and the VFD (Variable Frequency Driver also called the inverter) should be of stranded type and we use between 18 and 16 AWG.

    The total current is divided among the three coil wires, therefor a wire gauge of 16 should be sufficient.

    Currently we use 20AWG 4 conductor.

    Additional Information:


    Additional Information:



    Additional Information:



    Additional Information:

    Click the link to add information to this solution:
    What size of wire do you use to connect the VFD to the spindle?

  • I've buffered a PWM signal to a 0-10V analog signal and I would like to use that signal to run your 110V 2.2kW spindle and VFD. Could you please detail the correct wiring and VFD settings to get that working?

    This will depend on the VFD you have to identify the correct terminal. The terminal on the VFD will be labeled AI1 typically (Analog Input #1). You will also need to make sure to complete the PWM circuit using the GND terminal on the VFD.

    Additional Information:
    I have wired my 0-10V signal to the AI1 and GND terminals as suggested. I have also set the PD-01 and PD-02 settings to 1. Still nothing. Is there something else that I am missing?

    Additional Information:
    Thanks for the information. Can you let me know the model of the VFD that you have?

    Additional Information:
    VFD Model # YL600-2S-2K20

    Additional Information:
    Thanks. I will check our resources and documentation to see if there is another programming setting that needs to be changed.

    Additional Information:
    Does your VFD have a VI terminal?

    Additional Information:
    No, it does not. The terminals for this VFD are as follows (seperated by dashes "-").

    10V-AI1-AO2-PLC-DI5-DI3-DI1-COM
    AI2-GND-AO1-DI6-DI4-DI2-FM-24V

    Additional Information:
    Do you have a PD070 parameter?

    PD070 is the main Analog Input parameter.

    The options for that parameter is:
    0: 0-10V
    1: 0-5V
    2: 0-20mA
    3: 4-20mA
    4: 0-10V (4-20mA Stacked)
    5: XIA
    6: (VI+XIA)/2
    7: (3VA+XIA)/4
    8: (XIA_XIB)/2
    9: Max (XIA, XIB)
    10: Min (XIA, XIB)


    Additional Information:
    There is a PD-00 thru PD-09. PD-07 is currently set to 0.

    Additional Information:
    It appears that the manual I’m using “Titled YL600” is not the same as your unit. I will check our manuals and find the one that has only PD-00 to PD-09.

    Additional Information:
    For that VFD, the parameters are P0. The 0 may look like a D on the display.

    The parameters that need to be changed for the AI1 to work (Brackets [] around the correct selection):

    P0-01: First Motor Control Mode
    - 0: Sensorless Vector Control
    - 1: Flux Vector Control (FVC)
    - [2]: V/F Control

    P0-02: Options of Command Source
    - 0: Operation Panel Command Channel (LED will be off)
    - [1]: Terminal Command Channel (LED will be on)
    - 2: Communication Command Channel (LED will flicker)

    P0-03: Options of Principle Frequency Source X
    - 0: Digital Setting (Preset Frequency P0-08, UP/DOWN modifiable, no power-down memory)
    - 1: Digital Setting (Preset Frequency P0-08, UP/DOWN modifiable, with power-down memory)
    - [2]: AI1
    - 3: AI2
    - 4: AI3
    - 5: Pulse Setting (DI5)
    - 6: Multi Speed Instruction
    - 7: Simple PLC
    - 8: PID (Proportional Integral Derivative Control)
    - 9: Communication Given

    P0-11: Upper Limit Frequency Source
    - 0: P0-12 (Make sure the P0-12 parameter has the correct max frequency if used)
    - [1]: AI1
    - 2: AI2
    - 3: AI3
    - 4: Pulse Setting
    - 5: Communication Given

    P0-27: Command Source Bundle with Frequency Sources
    Single Digit: Options of Operation Panel Command Bundle with Frequency Sources
    - 0: No Bundling
    - 1: Digital Setting Frequency
    - [2]: AI1
    - 3: AI2
    - 4: AI3
    - 5: Pulse Setting (DI5)
    - 6: Multi Speed Instruction
    - 7: Simple PLC
    - 8: PID
    - 9: Communication Given
    Double Digit: Options of Terminal Command Bundle with Frequency Sources
    Hundred Place: Options of Communication Command Bundle with Frequency Sources
    Kilobit: Options of Automatic Operation Bundle with Frequency Sources

    P2-09: Upper Limit Source of Lower Torque Under Speed Control Mode
    - 0: Function Code P2-10 Setting
    - [1]: AI1
    - 2: AI2
    - 3: AI3
    - 4: Pulse Setting
    - 5: Communication Given
    - 6: MIN (Al1, Al2)
    - 7: MAX (Al1, Al2)
    - Maximum range for options 1-7, accords with P2-10

    If you elect to use a different AI#, then configure the parameters (P0-03, P0-11, P0-27 and P2-09) accordingly.

    Click the link to add information to this solution:
    I've buffered a PWM signal to a 0-10V analog signal and I would like to use that signal to run your 110V 2.2kW spindle and VFD. Could you please detail the correct wiring and VFD settings to get that working?

  • I WIRED MY VFD (2.2KW VERSION) AND TRIED TEST RUNNING THE SPINDLE. CONFIGURED TO YOUR SPECS ON THIS WEBSITE, ONLY ISSUE IS WE GOT AN ERROR CODE. ERR 02, DO YOU KNOW WHAT IS? OR HAVE A LIST OF CODES? THANK

    Can you provide the model number of your VFD?

    Yes, I have the "YL600 - 2S - 2K20"

    It just came with a small booklet that is all in Chinese...

    Click the link to add information to this solution:
    I WIRED MY VFD (2.2KW VERSION) AND TRIED TEST RUNNING THE SPINDLE. CONFIGURED TO YOUR SPECS ON THIS WEBSITE, ONLY ISSUE IS WE GOT AN ERROR CODE. ERR 02, DO YOU KNOW WHAT IS? OR HAVE A LIST OF CODES? THANK

  • When I start my spindle I get a emergency stop in Mach 3. I have run shielded cable and it is grounded at the VFD it is wired per you site instructions. any idea what to check

    You will definitely want to adjust your debounce setting in mach3 if your emergency or limit switch is engaging.

    Additional Information:
    Did you ever fix this issue? I am having the same problem.

    Additional Information:
    Did you ever fix this issue? I am having the same problem.

    Additional Information:
    Did you ever fix this issue? I am having the same problem.

    Additional Information:
    Did you ever fix this issue? I am having the same problem.

    Additional Information:
    Did you ever fix this issue? I am having the same problem.

    Additional Information:
    Did you ever fix this issue? I am having the same problem.

    Additional Information:
    Did you ever fix this issue? I am having the same problem.

    Additional Information:
    Did you ever fix this issue? I am having the same problem.

    Additional Information:
    Did you try changing the denounce setting?

    Additional Information:
    Meant to say denounce.

    Click the link to add information to this solution:
    When I start my spindle I get a emergency stop in Mach 3. I have run shielded cable and it is grounded at the VFD it is wired per you site instructions. any idea what to check

  • How can we check our 1.5kw spindle. we get a dL error after we start to cut. it spins up fine. We checked IGBTs in the VFD and they're not shorted. We suspect intermittent short INSIDE the spindle. What do you think?

    dL usually stand for a short that is occurring within the spindle or spindle wiring. I would recheck the wiring going from the VFD to the spindle, as well as the terminal on the spindle where there should've been some soldering required. We usually tend to either heat shrink or use electrical tape to cover the terminals so no contact or arching can be present.

    Also depending on the VFD you have please adjust the setting pd008, to the voltage that is required (110V/220V).

    If the issue proceeds please contact use at customerservice@buildyourcnc.com, for further assistance or replacement.

    Click the link to add information to this solution:
    How can we check our 1.5kw spindle. we get a dL error after we start to cut. it spins up fine. We checked IGBTs in the VFD and they're not shorted. We suspect intermittent short INSIDE the spindle. What do you think?

  • BUILDING ONE OF YOUR GREENBULL 6X LONG AND 2.2 KILOWATT SPINDLE DOES NOT FIT. SEEMS LEAD SCREW YOU SENT WITH KIT IS SHORT 42" LOOKS LIKE IT NEEDS TO BE 5 OR 6 INCH LONGER. THIS CORRECT? WHAT THE NEEDED LENGTH FOR UNIT?
  • I have a YL620 VFD and the 2.2 kw spindle. The programming that is on the buildyourcnc web site is different in the PO/PD parameters. Do you have the VFD settings for the parameters using the P00.00 format?
  • I have a YL600 VFD and the 2.2 kw spindle. The programming that is on the buildyourcnc web site is different in the PO/PD parameters. Do you have the VFD settings for the parameters using the P00.00 format0

    MY VFD SHOW E.O.C.A error


    Additional Information:
    EOCA light on my VFD


    Additional Information:


    Additional Information:

    Click the link to add information to this solution:
    I have a YL600 VFD and the 2.2 kw spindle. The programming that is on the buildyourcnc web site is different in the PO/PD parameters. Do you have the VFD settings for the parameters using the P00.00 format0

  • THE LEAD SCREW IS VERY HARD TO TURN. BACKLASH BUSHING SEEMS BE TOO TIGHT AND BINDING ON SCREW. DO IT NEED LUBRICATION OR DID DAMAGE NUT WHEN INSERTING SCREW?

    Yes, you can use lubrication, like 3-in-1 oil to make it a bit easier. You will need to run it up and down to break it in.

    Additional Information:

    Click the link to add information to this solution:
    THE LEAD SCREW IS VERY HARD TO TURN. BACKLASH BUSHING SEEMS BE TOO TIGHT AND BINDING ON SCREW. DO IT NEED LUBRICATION OR DID DAMAGE NUT WHEN INSERTING SCREW?

  • You state "If you purchase cabling, we will solder the cable to the spindle and connect the cable to the VFD." I didn't see that when I purchased my spindle and vfd. If I place an order for the wire and another female adapter, will you please solder the connector to the wire?

    When did you purchased the VFD and spindle? We only started this after the date of the instagram post that offered this added service.

    Additional Information:
    I purchased it July 16, 2020 however due to all the 2020 issues, I'm just now completing my CNC and hooking up the VFD and Spindle.

    Additional Information:
    The service started on Sept 23, 2020. Your order was prior to that.

    The soldering is straightforward. If you wish to have me provide this extra service, feel free to send the unit back with the cable and I will solder the cable and do the parameter check and test the VFD and spindle.

    Additional Information:
    When I purchased my VFD and Spindle, I forgot to purchase the wire for the spindle. I had an electrician run a 220 line and hook up the VFD. But I don't have the wire for the spindle. I'd like to get the one you recommend and just pay you for another connector and the soldering.

    Additional Information:
    Can I purchase the one you spindle wire you recommend and just pay you for another connector and the soldering.

    Click the link to add information to this solution:
    You state "If you purchase cabling, we will solder the cable to the spindle and connect the cable to the VFD." I didn't see that when I purchased my spindle and vfd. If I place an order for the wire and another female adapter, will you please solder the connector to the wire?

  • HEY ! I HAVE PURCHASED A VFD WITH MATCHING SPINDLE 1.5KW AND CONTROL PROGRAM UCCNC. MY INTERFACE CARD IS DB25, THE QUESTION HOW DO CONNECT TO DB25 SO THAT CAN SPEED UCCNC? SINCERELY "CNC BEGINNERS"

    Identify the Control Signals: First, determine which control signals from the DB25 interface card are used for spindle speed control. Typically, these are PWM (Pulse Width Modulation) signals or analog voltage signals.

    VFD Configuration: Your VFD should be configured to accept the type of control signal your DB25 card provides. This involves setting parameters in the VFD that correspond to the type of input signal it will receive for speed control.

    Wiring: Connect the appropriate output pins from the DB25 card to the input terminals on the VFD. This usually involves connecting the PWM or analog output to the corresponding input on the VFD. Make sure to consult the manuals for both your VFD and interface card for specific wiring details.

    UCCNC Settings: Configure UCCNC to output the correct type of signal (PWM or analog) that matches your VFD's configuration. This is done through the software's spindle setup section.

    Test and Adjust: Run some tests to ensure that the spindle speed is being correctly controlled by UCCNC. You might need to tweak settings in either the VFD or UCCNC for optimal performance.

    Click the link to add information to this solution:
    HEY ! I HAVE PURCHASED A VFD WITH MATCHING SPINDLE 1.5KW AND CONTROL PROGRAM UCCNC. MY INTERFACE CARD IS DB25, THE QUESTION HOW DO CONNECT TO DB25 SO THAT CAN SPEED UCCNC? SINCERELY "CNC BEGINNERS"

  • I purchased the 4.0kw spindle and VFD a while back, and have just installed a PMDX-107 controller... do you have any examples of the wiring connections for the SL-240EE to PMDX-107?

    If you want speed control, it is recommended to use the RS-485 connection on the VFD and use the control program such as Mach3 to communication serially with the VFD using this RS-485 connection.

    If you would rather use a controller such as the PMDX-107 to simulate the effect of a potentiometer using the Aref, Aout and Agnd and the Rev/Dir and Fwd/Run terminals to control operation and direction, you can connect those to the VFD.

    PMDX-107 Aout connects to the VI (analog voltage in). This is like the wiper on a potentiometer.
    PMDX-107 Agnd connects to the ACM terminal on the VFD for Analog common.
    PMDX-107 COM connects to DCM terminal on the VFD for Digital common.
    PMDX-107 Fwd/Run connects to the FOR terminal on the VFD for Forward.
    PMDX-107 Rev/Dir connects to the REV terminal on the VFD for Reverse.

    Refer to your PMDX-107 manual to correctly configure your dip switch settings and make sure to calibrate (tweak) the speed control using the trimmer next to the terminals on the PMDX-107.

    Click the link to add information to this solution:
    I purchased the 4.0kw spindle and VFD a while back, and have just installed a PMDX-107 controller... do you have any examples of the wiring connections for the SL-240EE to PMDX-107?

  • I HAVE YOUR MACH3 USB BOB, DO YOU GUYS SELL A TORCH CONTROL RELAY CAN WIRE UP TO TURN MY PLASMA ON AND OFF HOW WOULD WIFE THAT TOO THIS BOB?

    We do have a relay board that words like a standard relay.

    Here is the URL of the relay board that we offer:

    https://www.buildyourcnc.com/item/electronicsAndMotors-breakout-Relays-relay-board-250V-12A-5V

    Click the link to add information to this solution:
    I HAVE YOUR MACH3 USB BOB, DO YOU GUYS SELL A TORCH CONTROL RELAY CAN WIRE UP TO TURN MY PLASMA ON AND OFF HOW WOULD WIFE THAT TOO THIS BOB?

  • what is the warranty period and do you repair these in house? 2.2 kW (kilowatt) Water Cooled Spindle with Inverter (VFD)

    Spindles are generally covered up to 1 year after date of purchase. We do not repair them in house, but we do work with our manufacturer to replace defective units. Generally if you have a defective unit covered under warranty, we will issue a replacement.

    Click the link to add information to this solution:
    what is the warranty period and do you repair these in house? 2.2 kW (kilowatt) Water Cooled Spindle with Inverter (VFD)

  • What are the configuration settings for VFD for Spindle 1.5kW 110V. The search settings have a link for a 2.2kw spindle so I'm afraid they are the wrong ones and I don't want to fry the spindle. My VFD is an Huanyang HY01D511B.

    Did you get a manual for your VFD? Where did you purchase the VFD and spindle?

    Additional Information:
    I bought the VFD through Amazon with a similar spindle that you sell. The VFD came with a manual but unfortunately the spindle had all the model number and specs scratched off of it. In an attempt to set it up, I fried the spindle. I have complained to the vendor and to Amazon but have received no solution. If your spindle arrives with proper documentation I probably can set it up myself.

    Click the link to add information to this solution:
    What are the configuration settings for VFD for Spindle 1.5kW 110V. The search settings have a link for a 2.2kw spindle so I'm afraid they are the wrong ones and I don't want to fry the spindle. My VFD is an Huanyang HY01D511B.

  • I have the 2.2KW VFD. I would like to have it controlled through software. What are the Mode parameters that need to be changed that will allow FWD/ REV, START/STOP and RPM control?

    What controller are you using to control the cnc machine (Mach3 usb, parallel breakout board, etc.)?

    The spindle VFD has an input for 0-10 volts to control the speed and can be used with the MAch3 USB or the Pokeys57CNC board. There are also other terminals in the VFD to control the forwared/reverse and start and stop. Mach3 has parameters to control these output and you need to specify which pins are used for these.

    You can also use the TX/RX RS-485 connection on the VFD to have total control using an FTDI USB to serial connector board to connect the computer directly to the VFD.

    How to connect the USB to Serial adapter to the VFD:
    https://www.buildyourcnc.com/FAQ/13790

    FTDI USB to Serial:
    https://www.buildyourcnc.com/item/Interfaces-newbiehack-Interfaces-TTL232R-USB-UART-Serial

    Pokeys57CNC board:
    https://www.buildyourcnc.com/item/electronicsAndMotors-electronic-component-breakout-Mach4-mach3-USB-ethernet-Board

    Mach3 USB board:
    https://www.buildyourcnc.com/item/electronicsAndMotors-electronic-component-breakout-Mach3-USB-Board

    Parallel Breakout board:
    https://www.buildyourcnc.com/item/electronicsAndMotors-parallel-breakout-relay



    Additional Information:
    I do apologize for leaving out the parts list.
    Leadshine MX4660 4-Axis Digital Stepper Motor Driver
    Ethernet SmoothStepper
    YL600-2S-2K20 VFD
    4 Relay control board
    Has anyone had any success getting Mach3 to control the spindle speed and direction?

    Click the link to add information to this solution:
    I have the 2.2KW VFD. I would like to have it controlled through software. What are the Mode parameters that need to be changed that will allow FWD/ REV, START/STOP and RPM control?

  • THE GANTRY MOUNTED SPINDLE WATER COOLER PUMP THAT I PURCHASED DOES NOT OPERATE NO MATTER HOW CONNECT THREE WIRES TO TWO WIRE POWER SUPPLY.

    The 12V power supply has 3 terminals for AC in: N, L and earth ground. The output of the 12V power supply has 2 DC + and - terminals. Cut the connectors off of the ends of the fan and pump wires. Strip the red and black wires of both units. The fan will connect to the 12V power supply red to the + and black to the -. The pump will connect in the same way, but the white is not connected.

    If you have a pump that has a grey and black wire on the large connector, the grey is the 12VDC V+ wire and the black wire goes to the V-. The extra wire does not need to be connected.

    Click the link to add information to this solution:
    THE GANTRY MOUNTED SPINDLE WATER COOLER PUMP THAT I PURCHASED DOES NOT OPERATE NO MATTER HOW CONNECT THREE WIRES TO TWO WIRE POWER SUPPLY.

Get Help with:
This Product
Orders
Tech Support
Sales
This Product
Order Query
Tech Support
Sales
Not logged in. Log In Register
Track Order(s)
View Order(s)
I Want to Schecule a One-On-One Paid Tech Support Session
Book an Appointment Pertaining to a BuildYourCNC Product (Free)
Ask a Quesion Below (Free):
Book an Appointment Pertaining Other Equipment ($60/half hour)
Book an Immedite Appointment Pertaining Other Equipment ($120/half hour)
Ask a Quesion Below (Free):
Waiting for response... I may not answer immediately, but I was notified on my cellular phone so my response is forthcoming. If I don't respond immediately, you can always go to the [My Account] page to see all of our chats at any time.